Page 241 - Product-catalogue-v17
P. 241

Lightning & Surge Protection



        POWER PROTECTION - SURGE FILTERS


                                 TYPE 1+2 SURGE FILTERS
                                 SURGE PROTECTION AND LOW PASS FILTER
        Features:                 Imax            Iimp              Maximum   Voltage Protection                    1
           - All mode protection  (8/20μs)   In (8/20μs)   (10/350μs)   Connection   Load Current Level (3kA 8/20μs)   Alarm   Part No.
           - Safe metal enclosure  (kA)   (kA)    (kA)     Type     (A)       - Up (kV)    Contact
           - Three stages of protection  10  4    N/A      1+1      6         < 0.7        No     SFD1-6-10-275
           - Designed to protect    50    20      6.5      1+1      6         < 0.6        No     SFD1-6-50-275
          sensitive loads         50      20      6.25     1+1      10        < 0.6        No     SFD1-10-50-275
           - Standards IEC 61643-11,
          AS/NZS 1768             50      20      6.25     1+1      10        < 0.6        Yes    SFD1-10-50-275-A
                                  50      20      6.25     1+1      20        < 0.6        No     SFD1-20-50-275
                                  50      20      6.25     1+1      20        < 0.6        Yes    SFD1-20-50-275-A
                                  100     40      12.5     1+1      20        < 0.6        No     SFD1-20-100-275
                                  100     40      12.5     1+1      20        < 0.6        Yes    SFD1-20-100-275-A
                                  100     40      12.5     1+1      32        < 0.6        No     SFD1-32-100-275
                                  100     40      12.5     1+1      32        < 0.6        Yes    SFD1-32-100-275-A
                                  50      20      6.25     3+1      10        < 0.6        Yes    SFD3-10-50-275-A
               SFD1-20-100-275
                                  50      20      6.25     3+1      20        < 0.6        Yes    SFD3-20-50-275-A
                                  50      20      6.25     3+1      32        < 0.65       Yes    SFD3-32-50-275-A







              SFD3-20-50-275-A


                                 TYPE 2 COMPACT SURGE FILTER
                                 SURGE PROTECTION AND LOW PASS FILTER
                                  Imax            Iimp              Maximum   Voltage Protection
                                  (8/20μs)   In (8/20μs)   (10/350μs)   Connection   Load Current Level (3kA 8/20μs)   Alarm   Part No.
                                  (kA)    (kA)    (kA)     Type     (A)       - Up (kV)    Contact
                                  20      10      2 (N-PE)  1+1     20        < 0.6        No     SFDE1-20-20-275




                                 TYPE 2+3 ELV AC AND DC SURGE FILTERS
                                 SURGE PROTECTION AND LOW PASS FILTER
        Features:                 Imax            Iimp              Maximum   Voltage Protection
           - Multistage protection  (8/20μs)   In (8/20μs)   (10/350μs)   Connection   Load Current Level (3kA 8/20μs)   Alarm  Part No.
           - No earth leakage     (kA)    (kA)    (kA)     Type     (A)       - Up (kV)    Contact
           - Safe metal enclosure  12     8       N/A      2+0      10        < 0.18       Yes    IFD2-10-12-30
           - Installation independent   12  8     N/A      2+0      20        < 0.18       Yes    IFD2-20-12-30
          Performance
           - Standards IEC 61643-11,    3  1      N/A      2+0      6         < 0.08       No     IFD2-6-3-30
          AS/NZS 1768











                IFD2-20-12-30







                                               1300 556 601  |  ipd.com.au  |  V17-R04                       241
   236   237   238   239   240   241   242   243   244   245   246