Page 244 - Product-catalogue-v17
P. 244
Lightning & Surge Protection
POWER PROTECTION - SPECIAL APPLICATIONS
DEHN TYPE 2 FOR VARIABLE SPEED DRIVES AND WIND TURBINES
MOV SURGE ARRESTER
Features: Imax Prospective Voltage Signal
- Multi-purpose (8/20μs) In (8/20μs) Connection MCOV AC Fault Rating Protection Level C/O Part No.
- Pluggable design (kA) (kA) Type (V) (kArms) - Up (kV) Contact
- Heavy-duty zinc oxide varistor 25 15 1+0 600 25 ≤ 3 Yes DGSWE600FM
- Standards IEC/EN 61643-11
DGSWE600FM
DEHN TYPE 2 FOR LED STREET LIGHTING
COMPACT SURGE ARRESTER
Features: Imax Prospective Voltage Signal
- Visual fault indication (8/20μs) In (8/20μs) Connection MCOV AC Fault Rating Protection Level C/O Part No.
- Interruption of the load circuit (kA) (kA) Type (V) (kArms) - Up (kV) Contact
in the event of a fault 10 5 1+1 275 6 ≤ 1.5 No DCORL2P275SOIP
- Compact design
- Degree of protection: IP65
- Standards IEC/EN 61643-11
DCORL2P275SOIP
NOVARIS SURGE ARRESTER FOR RAILWAY POINT SYSTEMS
Features: Voltage
- DIN compliant fail-safe Imax In (8/20μs) Connection MCOV Protection Level Alarm
metal enclosure (8/20μs) (kA) Type (3kA 8/20μs) - Contact Part No.
- Modes of protection L-L, L-PE (kA) AC (V) DC (V) Up (kV)
- Standards IEC 61643-21 40 20 2+0 130 155 < 0.37 Yes SDD2-50-110-RPU
SDD2-50-110-RPU
NOVARIS EARTH CLAMPS
Features: Imax
- Active element is Gas (8/20μs) Spark Over Voltage DC (V) Voltage Protection Level Part No.
Discharge tube (GDT) (kA) (5kV 10/700μs) - Up (kV)
- 10mm² flying leads 100 230 < 0.9 EC100-230
- Prevent potential differences 100 350 < 1.0 EC100-350
- Bond earth isolated system
EC100-350
244 1300 556 601 | ipd.com.au | V17-R04