Multi-function Meters
M1M 15 M1M 20 M1M 30 M4M 20 M4M 30 M4M 2X
Accuracy Class 1 1, 0.5S (M1M 20 I/O) 1, 0.5S (M1M 30 I/O) 0.5S 0.5S 0.5S
Measured Parameter
TRMS Current & Voltage • • • • • •
Frequency • • • • • •
Active power, Power factor • • • • • •
Reactive and Apparent power • • • • • •
Operating timer, countdown timer • • • • • •
On hours - - - - - -
Load hours - - - - - - 2
Active energy • • • • • •
Reactive and Apparent energy • • • • • •
4 quadrants energy (Import/Export) - • • • • •
Tariffs - - - - • -
Power Quality
THD (I, VLN, VLL) - • • • • •
Individual harmonics - - 40 th - 40 th 25 th
Neutral current - Calculated Calculated Calculated Measured Calculated
Phasors (I, VLN) - - - - • -
Unbalances and waveforms (I, VLN, VLL) - - • - • • (Unbalances)
Measurement Accuracy
Voltage Class 1 (IEC 61557-12) Class 0.5 (IEC 61557-12) Class 0.5 (IEC 61557-12) Class 0.2 (IEC 61557-12) Class 0.2 (IEC 61557-12) Class 0.2 (IEC 61557-12)
Class 1 (IEC 61557-12)
Current Class 0.5 (IEC 61557-12) Class 0.5 (IEC 61557-12) Class 0.2 (IEC 61557-12) Class 0.2 (IEC 61557-12) Class 0.2 (IEC 61557-12)
Class 1 (IEC 61557-12) Class 1 (IEC 61557-12) Class 1 (IEC 61557-12)
Active power Class 0.5 (IEC 61557-12 ) Class 0.5 (IEC 61557-12 ) Class 0.5 (IEC 61557-12 ) Class 0.5 (IEC 61557-12) Class 0.5 (IEC 61557-12) Class 0.5 (IEC 61557-12)
(M1M 20 I/O, M1M 30 I/O) (M1M 20 I/O, M1M 30 I/O) (M1M 20 I/O, M1M 30 I/O)
Reactive power Class 2 (IEC 61557-12) Class 2 (IEC 61557-12) Class 2 (IEC 61557-12) Class 2 (IEC 61557-12) Class 1 (IEC 61557-12) Class 1 (IEC 61557-12)
Data Recording and Logs
Single alarms - 15 15 25 25 25
Warnings, alarms and errors logs - • • • • •
Complex alarms with logics - - - - 4 -
Min/Max and average demand values - - Basic Basic Advanced Basic
Energy trending logs - - • - • -
RTC - - • - • •
Voltage Measurement Inputs
Measurement range 80 - 265V AC (L-N) 80 - 265V AC (L-N) 80 - 265V AC (L-N) 50 - 400V AC (L-N), 87 - 690V AC (L-L) 50 - 400V AC (L-N), 87 - 690V AC (L-L) 50 - 400V AC (L-N), 87 - 690V AC (L-L)
Rated frequency, 50 - 60Hz
• • • • • •
HMI
Graphs visualisation - - - Basic Advanced -
Notifications and password protection • • • • • -
Homepage and favourite page - - - • • -
Current Measurement Inputs
Measurement range 50mA - 6A 50mA - 6A 50mA - 6A 10mA - 6A 10mA - 6A 10mA - 6A
5A (Class 0.5S) 5A (Class 0.5S) 5A (Class 0.5S) 5A (Class 0.5S) 5A (Class 0.5S) 5A (Class 0.5S)
CT secondary
1A (Class 1) 1A (Class 1) 1A (Class 1) 1A (Class 0.5S) 1A (Class 0.5S) 1A (Class 0.5S)
Connectivity
Automatic integration in ABB Ability™ EDCS - - - • • •
Bluetooth Low Energy - - - • • •
User Interface
LED Display • - - - - -
LED digit height (mm) 10 - - - - -
Communication Modbus RTU Modbus RTU, Modbus TCP/IP Modbus RTU, Modbus TCP/IP Modbus RTU, Modbus TCP/IP, Modbus RTU, Modbus TCP/IP, Modbus RTU, Modbus TCP/IP
PROFIBUS DP-V0, BACnet/IP PROFIBUS DP-V0, BACnet/IP
RJ45 Daisy Chain (Ethernet version) - - - - • •
Mechanical Characteristics
96 x 96 x 85 96 x 96 x 85 96 x 96 x 85 96 x 96 x 77 96 x 96 x 77 96 x 96 x 77
Overall dimensions (mm)
(Depth inside the switchboard: 65mm) (Depth inside the switchboard: 65mm) (Depth inside the switchboard: 65mm) (Depth inside the switchboard: 57mm) (Depth inside the switchboard: 57mm) (DIN Rail mounting)
IP rating IP54 IP54 IP54 IP54 IP54 IP54
Climatic Conditions
-5°C to 55°C -5°C to 55°C -5°C to 55°C -25°C to 70°C -25°C to 70°C -25°C to 70°C
Operating temperature
(K55 according to IEC 61557-12) (K55 according to IEC 61557-12) (K55 according to IEC 61557-12) (K70 according to IEC 61557-12) (K70 according to IEC 61557-12) (K70 according to IEC 61557-12)
-25°C to 70°C -25°C to 70°C -25°C to 70°C -40°C to 85°C -40°C to 85°C -40°C to 85°C
Storage temperature
(K55 according to IEC 61557-12) (K55 according to IEC 61557-12) (K55 according to IEC 61557-12) (K70 according to IEC 61557-12) (K70 according to IEC 61557-12) (K70 according to IEC 61557-12)
Pollution degree 2 2 2 2 2 2
Standards
Electrical safety IEC 61010-1 • • • • • •
1300 556 601 | ipd.com.au | V17-R05 299