3 x 230/400 V  KNX                         3 x 230/400 V  KNX
                           KNX                                        KNX
                   M           SDB KNX                        M           SDB KNX
                 SEB                                        SEB





                                                              Type                     Part No.
              shielded duct or metal pipe connected           DV ZP TNC 255 (TN-C system)  900 390
              to the main earthing terminal on both ends
                                                              DV ZP TT 255  (TN-S/TT system)  900 391
                                                              DG M TNS 275  (TN-S system)  952 400
                                                              DG M TT 275  (TT system)  952 310
                                                              BT 24                     925 001
       Figure 9.10.5  Lightning equipotential bonding is not required for the KNX cable due to zone expansion











                                                               KNX
                                            3 x 230/400 V  SDB KNX



                               M
                                                              Type                     Part No.
                         SEB
                                                              DV ZP TNC 255 (TN-C system)  900 390
                                                              DV ZP TT 255  (TN-S/TT system)  900 391
                                                              DG M TNS 275  (TN-S system)  952 400
                                                              DG M TT 275  (TT system)  952 310
                                                              BT 24                     925 001

       Figure 9.10.6   Lightning current arresters installed in the main power supply system and surge arresters installed at the distribution board of
                the KNX system



            www.dehn-international.com                             LIGHTNING PROTECTION GUIDE  315