          Figure 9.10.7  Surge protective devices installed at the main distribution board and at the distribution board of the KNX system


          Independent of the point of strike, surge protective devices al-  Due to the high dielectric strength of the bus cable, it is unlike-
          ways have to be installed at the distribution board of the KNX   ly that short bus cables with isolated sensors (e.g. in a socket
          system (Figures 9.10.6 and 9.10.7).          outlet combination without earthed installation devices) are
                                                       destroyed. In this case, it is not necessary to install surge arrest-
                                                       ers directly at the bus devices (Figures 9.10.6 and 9.10.7).






































          316  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com