Page 387 - 35_DS702_E_2014_Lightning_Protection_Guide
P. 387

in parallel with a low-voltage cable. However, a distance of
                                             230 V     10 mm must be kept after removing the J-Y(ST)Y cable sheath.
                                                       Loops are also formed if a node is attached to a metallic con-
                                                       struction / pipe which is connected to the main earthing bus-
                   node                                bar (Figure 9.20.3). Also in this case, it is advisable to route
                           induction loop  MEB         the cables as close as possible to the construction / pipe.

                                                       Surge protection in case of a combination topology
                                                       If the inputs / outputs connected to the node are located in
                                                       close proximity to the node, surge protective devices are not
                                                       required.
          Figure 9.20.3  Induction loop caused by a magnetic valve attached
                   to a metallic pipe                  Figure 9.20.4  shows  surge  protective  devices  for  LPTs
                                                       which are supplied by means of a two-wire bus cable. Figure
                                                       9.20.5 shows surge protective devices for directly supplied
          proximity to one another (Figure 9.20.2). If a J-Y(ST)Y cable   FTTs (typically 24 V d.c.) in case of long connecting cables of
          has a dielectric strength of 2.5 kV, this cable can be connected   power supply units.
















                               ϑ                                            ϑ
              230 V                                         230 V

                              node                                         node


                     LON                                          LON




                                                        No.  Surge protective device      Part No.
                                                            BXT ML2 BD S 48               920 245
          No.  Surge protective device      Part No.        + BXT BAS                     920 300
               BXT ML2 BD S 48               920 245        see    (lightning equipotential bonding)
               + BXT BAS                     920 300
                                                            DR M 2P 255                   953 200
               see    (lightning equipotential bonding)
                                                            BXT ML2 BE S 24               920 224
               DR M 2P 255                   953 200        + BXT BAS                     920 300

          Figure 9.20.4  Surge protective devices for an LPT in a combination   Figure 9.20.5  Surge protective devices for an FTT in a combination
                   topology extending beyond buildings           topology extending beyond buildings







          386  LIGHTNING PROTECTION GUIDE                            www.dehn-international.com
   382   383   384   385   386   387   388   389   390   391   392