Type Part No. Max. continuous Nominal SPD class Approval
operating DC voltage U current I
C L HazLoc SIL ATEX IEC Ex UL CSA EAC
BXT ML4 B 180 920 310 180 V 1.2 A 1) 1 • • • • – • •
BXT ML4 BE 5 920 320 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BE 12 920 322 5 V 0.75 A 1) 1 • • • • • • •
BXT ML4 BE 24 920 324 33 V 0.75 A 1) 1 • • • • • • •
BXT ML4 BE 36 920 336 45 V 1.8 A 1) 1 • • • • • – •
BXT ML4 BE 48 920 325 54 V 0.75 A 1) 1 • • • • • • •
BXT ML4 BE 60 920 326 70 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BE 180 920 327 180 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 5 920 340 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 12 920 342 15 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 24 920 344 33 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 48 920 345 54 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 60 920 346 70 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD 180 920 347 180 V 0.75 A 1) 1 • • • • • • •
BXT ML4 BC 5 920 350 6.0 V 1.0 A 1) 1 • • • • – • •
BXT ML4 BC 24 920 354 33 V 0.75 A 1) 1 • • • • – • •
BXT ML4 BE C 12 920 362 15 V 0.1 A 1) 1 • • • • – – •
BXT ML4 BE C 24 920 364 33 V 0.1 A 1) 1 • • • • – • •
BXT ML4 BE HF 5 920 370 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD HF 5 920 371 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML4 BD HF 24 920 375 33 V 1.0 A 1) 1 • • • • • • •
BXT ML2 B 180 920 211 180 V 1.2 A 1) 1 • • • • – • •
BXT ML2 BD 180 920 247 180 V 0.75 A 1) 1 • • • • – • •
BXT ML2 BE S 5 920 220 6.0 V 1.0 A 1) 1 • • • • – • •
BXT ML2 BE S 12 920 222 15 V 0.75 A 1) 1 • • • • – • •
BXT ML2 BE S 24 920 224 33 V 0.75 A 1) 1 • • • • – • •
BXT ML2 BE S 36 920 226 45 V 1.8 A 1) 1 – • – – • – •
BXT ML2 BE S 48 920 225 54 V 0.75 A 1) 1 • • • • • • •
BXT ML2 BD S 5 920 240 6.0 V 1.0 A 1) 1 • • • • – • •
BXT ML2 BD S 12 920 242 15 V 1.0 A 1) 1 • • • • – • •
BXT ML2 BD S 24 920 244 33 V 1.0 A 1) 1 • • • • – • •
BXT ML2 BD S 48 920 245 54 V 1.0 A 1) 1 • • • • – • •
BXT ML2 BE HFS 5 920 270 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML2 BD HFS 5 920 271 6.0 V 1.0 A 1) 1 • • • • • • •
BXT ML2 BD DL S 15 920 243 17 V 0.4 A 2) 1 • • • • – – •
BXT ML4 BPD 24 920 314 33 V 0.1 A 2) 1 – • – – – – •
BXT M2 BD HC5A 24 920 296 36 V 5 A 3) 1 – • – – – – •
BXT ML4 BE BD 24 920 334 33 V 0.75 A 1) 1 – – – – – – •
BXT ML4 MY 110 920 388 Line - PG 85 V 3 A 3) 2 – • – – – – •
BXT ML4 MY 250 920 389 Line - PG 320 V 3 A 3) 2 – • – – – – •
BXT ML2 MY E 110 920 288 Line - PG 85 V 3 A 3) 2 – • – – – – •
BXT ML2 MY 250 920 289 Line - PG 320 V 3 A 3) 2 – • – – – – •
BXT ML4 BD EX 24 4) 920 381 33 V 0.5 A 3) 2 • • • • – • •
BXT ML2 BD S EX 24 4) 920 280 33 V 0.5 A 3) 2 • • • • – – •
BXT ML4 BC EX 24 4) 920 384 33 V 0.5 A 3) 2 • • • • – • •
BXT ML2 BD HF EX 6 4) 920 538 6 V 4.8 A 3) 2 • • • • – – •
1) at 45 °C at 70 °C at 80 °C
2)
3)
Protection modules can be plugged into the universal base parts BXT BAS (Part No. 920 300)
BSP BAS 4 (Part No. 926 304)
4) BXT BAS EX (Part No. 920 301)
SIL Safety Integrity Level (Germany)
ATEX Explosionsschutz/EU CSA Canadian Standards Association/CDN IEC Ex International Electrotechnical Commission System
8 EAC Eurasian Conformity UL Underwriters Laboratories Inc./USA HazLoc CSA and USA Hazardous Location Standard