Page 44 - ACB-E1.2-E2.2-E4.2-E6.2
P. 44
ABB | SACE Emax 2
Ekip Touch - Settings
1 - Main settings
Foreword All the following parameters are available either directly, or from the Settings menu, in the conditions
established by Ekip Touch on the basis of the version and configuration described.
Consult manual 1SDH001330R1002 for any Main settings in the menu which are not described below
and for the Integrative settings (available by accessing the unit by means of a service connector via Ekip
Connect or by communication via system bus):
• Circuit-breaker: Hardware Trip, T Protection, Neutral Protection
• Phase Sequence
• Monitor time
• Power Controller
• Load Shedding
• Network Analyzer
• Datalogger
• Dual Set
• Functions
• View
• Maintenance
• Programmable states
• Filters
• TAG Name, User data, Clients Page
• Led Alive
• Supplementary settings for commands, zone selectivity, Wizard
WARNING! changes to the settings must be made in the absence of protection alarms
Configuration The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be
activated, is available for the 3P CB.
Activation of the configuration with External neutral (3P + N) enables:
• histograms of phase Ne in the Histograms page
• neutral current measurements
• submenu for configuring the Neutral protection (Neutral Protection)
• neutral current recording in the case of TRIP
With 3P CB, the parameter is set by default as: 3P.
Ground protection In the earth Circuit-breaker-Protections menu of the LSIG version of Ekip Touch you can:
• activate/deactivate the presence of external toroid S.G.R and relative Gext protection.
• activate the presence of Rc Toroid and relative protection.
• activate/deactivate the MDGF transformer presence and relative MDGF protection.
NOTE: Rc Toroid can be activated if the Measuring Measurements package and Rc version
Rating plug are present; Toroid presence in the menu can only be deactivated afterwards
by replacing the installed Rating plug
With Ekip Touch LSIG, the parameter is set by default as: Absent.
Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and
60 Hz.
NOTE: the measurements are taken on the basis of the set grid frequency: incorrect
configuration of the parameter may lead to abnormal measurements and protection
Ekip Touch is supplied with the parameter setting that suits the ordered configuration.
42 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Ekip Touch - Settings | 1 - Main settings