Page 39 - ACB-E1.2-E2.2-E4.2-E6.2
P. 39

ABB | SACE Emax 2

       9 - Additional protections and functions



              Additional protections Some protections have additional functions which extend their characteristics and performance:
                                     Name     Description                             Protections
                                     Thermal   Reduced trip time in the case of TRIPs within brief   L, S
                                     Memory   intervals (protection against cable overheating)
                                              Additional parameters for managing TRIP
                                     Zone
                                     selectivity  commands between circuit-breakers equipped   S, S2, G, D, Gext, MDGF
                                              with the same function
                                                                                      S, I, G, MCR, S2, D, S(V), S2(V), UV,
                                              Blocking of protection on the basis of   OV, VU, UV2, OV2, UP, OP, RP, RQ,
                                     Blocks
                                              programmable events                     OQ, RV, UF, OF, UF2, OF2, ROCOF,
                                                                                      Gext, MDGF
                                              Different threshold of the protection for a
                                     Startup  limited time, with activation on the basis of a   S, I, G, S2, D, UP, Gext, MDGF
                                              programmable monitoring threshold




              Additional protections Installation of certain accessories allows the additional protections to be activated:
                                                                  Th-           Fun-
                                     Name      Type of protection        Time          Additional functions
                                                                  reshold       ction
                                               Earth fault with current                Trip enable, Zone Selectivity,
                                     Gext      reading by S.G.R.                       Startup enable, Locking, Pre-alarm
                                               external sensor                         threshold
                                               Residual current with
                                     Rc        corrent reading by
                                               external toroid Rc
                                               Synchronism between
                                               two independent
                                     Synchrocheck voltage sources or
                                               energizing of a busbar
                                               not active
                                               Earth fault with current                Trip enable, Zone Selectivity,
                                     MDGF      reading by MDGF                         Startup enable, Locking, Pre-alarm
                                               external sensor                         threshold


                                    Further details about the protections are given in document 1SDH001330R1002.


        Programmable Functions and  Ekip Touch has eight programmable commands, which activate on the basis of signals or events. Each
                        Commands command allows the activation function and event monitoring time to be programmed.
                                     Name               Description                            Menu path
                                     External Trip      Sends a TRIP command
                                     RESET Trip         TRIP signal reset                      Advanced - Functions
                                     Activate SET B     Changes the protections set, from Set A to Set B
                                     Energy RESET       Resets the energy meters               Measurements - Energy
                                     Command YO         Sends a command to opening coil YO
                                     Command YC         Sends a command to closing coil YC     Settings - Functions
                                                        Changes the configuration, from Remote to
                                     LOCAL Switch On                                           Settings - Modules
                                                        Local                                  - Functions
                                     Signaling RESET    Reset the contacts of the signalling modules














       37 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                   Protections | 9 - Additional protections and functions