Page 48 - ACB-E1.2-E2.2-E4.2-E6.2
P. 48

ABB | SACE Emax 2

                  Ekip Signalling 4K The menu activates in the presence of module Ekip Signalling 2K and auxiliary power supply.
                                    The Autotest command is available in the menu; it activates the automatic output test sequence (contacts
                                    and leds) and provides for the following operations:
                                     •  Opening of the output contacts and switching off of output leds
                                     •  Closing in sequence of the four output contacts and switching on of the relative leds
                                     •  Reset initial conditions
                                           IMPORTANT: the Autotest command closes the contacts regardless of the configuration
                                           set by the user: the user is responsible for making the devices connected to the modules
                                           secure, checking that the contacts have closed properly and that the leds have come on



                  Ekip Signalling 2K The menu activates in the presence of module Ekip Signalling 2K, auxiliary power supply and local bus
                                    enabled.
                                           NOTE: a menu is available for each Ekip Signalling 2K module present, up to a maximum of
                                           three
                                    The Autotest command is available in each submenu; it activates the automatic output test (Contacts and
                                    leds), input test (leds) and provides for the following operations:
                                      1.   Resetting of output contacts (= open) and leds (= off).
                                      2.  Lighting up of all leds in sequence (output and input)
                                      3.  Closing and switch-off in sequence of the two output contacts while the relative leds come on.
                                      4.  Reset initial conditions
                                           IMPORTANT: the Autotest command closes the contacts regardless of the configuration
                                           set by the user: the user is responsible for making the devices connected to the Ekip
                                           Signalling 2K modules secure, checking that the contacts have closed properly and that
                                           the leds have come on



                    ZoneSelectivity The menu has one or two sections, visibility of which depends on the protections available and enabled:
                                     Submenus                  Reference selectivity     Outputs/Inputs managed
                                     S Selectivity             S, S2, D (Forward)        SZi (DFi), SZo (DFo)
                                     G Selectivity             G, Gext, MDGF, D (Backward)  GZi (DBi), GZo (DBo)

                                    Each submenu has three fields for checking selectivity inputs and outputs:

                                     Field                     Description
                                     Input                     Provides the status of the selectivity input (On/Off)
                                     Force output              Selectivity output activated
                                     Force Output              Selectivity output deactivated

                                    Consult the description of the putting into service procedure in the documents when checking the
                                    selectivity contacts 1SDH000999R0002 and 1SDH001000R0002.


                            RC test The command is available in the presence of Rating plug Rc and Rc toroid.
                                    Selection of the command accesses a window containing the protection settings and test instructions:
                                      1.   Press the iTEST button to send a test signal to the toroid.
                                      2.  The toroid sends Ekip Touch a signal as though it had measured an alarm current.
                                      3.  Ekip Touch sends a TRIP command.
                                           IMPORTANT: the command sends a signal to the Rc toroid and concludes with a TRIP
                                           command: the user is responsible for checking that the initial connections are correct
                                           (of the toroid and power supplies of the unit) and that TRIP is accomplished













       46 | © 2022 ABB |  1SDH001316R1002 - ECN000232533                                       Ekip Touch - Test | 1 - Test
   43   44   45   46   47   48   49   50   51   52   53