Page 43 - ACB-E1.2-E2.2-E4.2-E6.2
P. 43

ABB | SACE Emax 2

       3 - Class 1 Power & Energy Metering



               List and performance Presence of the  Class 1 Power & Energy Metering package allows higher measuring accuracy to be
                                    obtained for the following quantities:
                                                                                   Normal operating   Accuracy of
                                     Measurement      Monitor time (min-max)
                                                                                   range              read value
                                                                                  Standard IEC 61557-12,
                                     Phase currents  (6) (8)  0,004 ÷ 64 In                           0,5 %   (1)
                                                                                  tables 20-22
                                     Internal earth fault   0,08 ÷ 64 In          Standard IEC 61557-12,   0,5 %   (1)
                                     current  (2)                                 table 20
                                     Line frequency   30 ÷ 80 Hz   (3)            fn ± 10 %   (4)     ± 0,02 Hz
                                     Total active and   |Pmin ÷ Pmax|  (5)        Standard IEC 61557-12,   1 %   (1)
                                     apparent power  (7)                          tables 8-11-14
                                     Active and apparent          (5)             Standard IEC 61557-12,    (1)
                                     phase power      |Pmin ÷ Pmax|               tables 8-11-14      1 %
                                     Total active and   1 kWh ÷ 2 TWh; 1 kVARh ÷ 2 TVARh;  Standard IEC 61557-12,    (1)
                                     apparent energy  1 kVAh ÷ 2 TVAh             tables 8-11-14      1 %
                                                                                  Standard IEC 61557-12,
                                     Power factor     0,5 ÷ 1                                         1%   (1)
                                                                                  table 27
                                    (1)  the accuracy values refer to the normal operating intervals and conditions established by IEC
                                    61557-12, for each quantity and class declared
                                    (2)  available with LSIG versions
                                    (3)  available for voltage values of over 30 V (with Un < 277 V) or 60 V (with Un ≥ 277 V)
                                    (4)  47 ÷ 55 Hz with fn = 50 Hz; 54 ÷ 66 Hz with fn = 60 Hz
                                    (5)  Pmin = 0,5 In x 5 V; Pmax= 3 x 16 In x 900 V
                                    (6)  the higher phase currents are also available in the Histograms, Measuring instruments and
                                    Measurement summary pages
                                    (7)  the higher total powers are also available in the Measuring instruments and Measurement
                                    summary pages
                                    (8)  internal phase current; in the presence of an external Neutral, the accuracy of current Ne is 1%


           Functional characteristics The measuring performance of the  Class 1 Power & Energy Metering package is guaranteed in the
                                    following conditions (from table 43 of standard IEC 61557-12):
                                     Characteristic                        Value
                                     Classification of performance measuring and
                                     monitoring device (PMD) in accordance with   PMD-DD
                                     chapter 4.3 of the standard
                                                                          Operating: T= -25°C to +70°C; Storage: T = -30°C
                                     Temperature
                                                                          to +70°C; Class: K70
                                                                          Up to 90% relative humidity without
                                     humidity and altitude
                                                                          condensation; From 0 to 2000 meters
                                     Performance class for active energy and power 1




                   Information page Presence of the Class 1 Power & Energy Metering package activates the IEC 61557-12 information page,
                                    which can be consulted in the About menu













                                    Figure 21

                                    The page shows the activation state of the  Class 1 Power & Energy Metering package (Activated/
                                    Deactivated) and the serial numbers of certain accessories installed on the CB for the specific purpose of
                                    conforming to the characteristics of the package (electronic units and internal current sensors)


       41 | © 2022 ABB |  1SDH001316R1002 - ECN000232533          Ekip Touch - Measurements | 3 - Class 1 Power & Energy Metering