Continued from the previous page                                ABB | SACE Emax 2
                                     Fault            Possible causes               Suggestions
                                                      Current below the minimum     Correct operating condition.
                                                      threshold that can be displayed
                                                      Incorrect frequency setting   Set frequency
                                     Measurements     Harmonic distortion and/or crest
                                     incorrect or absent   factor off range         Correct operating condition.
                                     (current, voltage,   Incorrect connection between   Check connections between isolation
                                     etc)             isolation transformer and     transformer and Measurement
                                                      Measurement module            module
                                                      Rated Voltage parameter setting
                                                      error                         Set the correct parameters
                                                      The PIN has been disabled or has
                                     The PIN is not   already been entered in the same   Operating condition correct; consult
                                     required                                       chapter relating to the PIN
                                                      programming session
                                                                                    Contact ABB or consult document
                                     PIN error        PIN wrong or lost
                                                                                    1SDH001501R0001
                                                                                    Check Trip coil connection and
                                                      Trip coil is not connected properly  messages on display
                                     It is not possible to   CB trip signal has not been reset  Press the reset pushbutton
                                     perform the trip test
                                                      The busbar current is greater than   Correct operating condition.
                                                      zero
                                                                                    1. If closed, open CB in the manual
                                                                                    mode and check changed status.
                                                                                    2. Press iTest, check that the signal
                                                                                    has disappeared from the display and
                                                      One or more of the following
                                     TRIP fail signaling:   conditions:             the general status of the alarms.
                                     Trip Fail command    • Trip coil not working   3. Check the conditions of the wiring
                                                                                    and internal contacts
                                     (BF)              • status contacts not working  4. Working in safety conditions, close
                                                       • faulty internal wiring
                                                                                    the CB and perform a trip test via the
                                                                                    trip unit

                                                                                    Contact ABB if problems persist
                                     The expected trip   Trip excluded              Operating condition correct; enable
                                     does not occur                                 trip if necessary
                                                      Wrong threshold/time/curve selected Correct parameters
                                     Trip times different  Thermal memory enabled   Disable it if it is not necessary
                                     than expected    Zone selectivity enabled      Disable it if it is not necessary
                                                      Incorrect neutral selection   Modify the neutral selection
                                     Rapid trip with   linst trip                   Correct operating condition with
                                     I3=Off                                         short circuit at high current
                                     High ground-fault   Incorrect selection of the sensor  Set internal or external sensor
                                     current, but no trip   Function G inhibited owing to high   Operating condition correct (see
                                     occurs           current                       protection description chapter)
                                     Opening data not   No auxiliary power supply and/or
                                     displayed        battery low                   Correct operating condition.