Continued from the previous page                                ABB | SACE Emax 2
                                    Protections
                                    In the event of protection or measurement alarms, the associated signals are reported:
                                     Signal                     Type of alarm
                                     Trip Test                  Trip test performed signal. Press iTEST to reset the message
                                     Protection timing (for example: L   Specific protection in time delay mode
                                     timing)
                                     Protection prealarm (for example:   Specific protection in prealarm
                                     Prealarm G)
                                     Protection (Trip off) [for example:  Specific protection, configured with trip disabled, in alarm
                                     S (Trip off) ]             state
                                     2I Protection Active       2I Protection active
                                     Load LC1 / Load LC2        Current threshold 1 I1 / 2 I1 exceeded and in alarm state
                                     Iw1 Warning / Iw2 Warning  Current threshold Iw1 / Iw2 exceeded and in alarm state
                                     Harmonic dist.             Harmonic Distortion protection in alarm state
                                     Power factor               Power factor measurement (cos φ) less than set threshold
                                     Phase cycle                Phase sequence protection in alarm state
                                     Frequency                  Frequency measured off range (<30 Hz or >80 Hz)
                                     5th harmonic above Th / I sopra
                                     Th / THD I above Th / THD V   Single or total harmonic measurement above threshold
                                     above Th




         Faults, causes and remedies A list of possible faulty situations for Ekip Touch, their possible causes and suggestions about how to
                                    resolve them are given below. Integrate the table with that of the circuit-breaker available in manuals
                                    1SDH000999R0002 and 1SDH001000R0002.
                                           NOTE: check error messages on display before consulting the table; if the suggestions given
                                           fail to resolve the problem, call the ABB assistance service and provide the report produced
                                           by the Ekip Connect software if possible

                                     Fault            Possible causes               Suggestions
                                     Communication    Circuit-breaker in withdrawn position,
                                     problems with    Vaux absent or modules not inserted   Insert modules, set CB to Connected
                                     modules in terminal                            position, connect Vaux
                                     box              properly
                                     CB status not
                                     aligned with CB   Absence of terminal box modules or   Check for presence of terminal box
                                     position         of contact S75I               modules and connect contact S75/I
                                                      The connections or supplies of the
                                                      opening/closing actuators are not   Check connections and supplies.
                                     Circuit-breaker fails   correct
                                     to react to opening/ Absence of auxiliary power supply to  Check supplies and status of Power
                                     closing command   Ekip Touch                   LEDs
                                     from Ekip Touch                                Check circuit-breaker documentation
                                                      Circuit-breaker is in a condition which   and cases that fail to enable
                                                      fails to enable the selected command
                                                                                    command
                                                      No auxiliary supply or currents lower
                                     Display off and/or   than minimum turn-on values  Correct operating condition.
                                     not backlit
                                                      Temperature outside range     Correct operating condition.