Page 52 - ACB-E1.2-E2.2-E4.2-E6.2
P. 52
ABB | SACE Emax 2
Ekip Touch - Default
1 - Ekip TOUCH default parameters
Protections All Ekip Touch models are supplied with the protections (and relative correlated functions) off, with the
exception of the protections listed below:
Protection Configuration
I1= 1 In; t1= 12 s; curve= t= k/I ; prealarm: 90% I1I1= 1 In;
2
L (excluding Ekip M Touch)
t1= 48 s; curve= t= k/I ; prealarm: 90% I1
2
I1= 1 In; t1= 22 s (Class= 10E); Thermal Memory= On;
L (only Ekip M Touch) Prealarm: 90 % I1I1= 0,4 In; t1= 45 s (Class= 20E); Thermal
Memory= On; Prealarm: 90 % I1
L (1) I1= 1 In; t1= 144 s; curve= t= k/I ; prealarm: 90% I1
2
I3= 5.5 In (all except Ekip M Touch) / 6 In (Ekip M Touch);
I
startup= OFF
I I3= 4 In; startup= OFF
Harmonic distortion On
Rc (1) Idn= 3 A; Tdn= 0,06 s
Rc (2) Idn= 3 A; Tdn= 0,06 s
(1) protection always active; a model L Disable rating Plug must be used to disable it
(1)(2) protection available and active if model Rc Rating Plus is present
Parameters Unless different specifications are requested when ordering, all Ekip Touch models are supplied with the
following configurations:
Parameters Configuration
Frequency 50 Hz (IEC) / 60 Hz (UL)
Configuration 3P (3P circuit-breaker) / 4P (4P circuit-breaker)
Neutral Off (3P circuit-breaker) / 50% (4P circuit-breaker)
Rated voltage 400 V
Power flow Bottom → Top
Phase Sequence 1-2-3
Local bus Off
Mode Local
Language English
Bluetooth Low Energy Off
Password 00001
Home page Histograms
Led Alive Disabled
View Horizontal
Maintenance On
Test Bus On
Modbus RTU par Address: 247; baudrate: 19.2 kbit/s
Profibus Address: 125
DeviceNet TM MAC ID: 63; baudrate: 125 kbit/s
Modbus TCP/IP Static IP: 0.0.0.0
50 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Ekip Touch - Default | 1 - Ekip TOUCH default parameters