Page 53 - ACB-E1.2-E2.2-E4.2-E6.2
P. 53

ABB | SACE Emax 2
        Management operations




       1 - Ekip Touch maintenance and troubleshooting



                       Introduction Correct maintenance of the unit and connected devices ensures they operate correctly over time.
                                    The maintenance operations must be performed by expert personnel, as required by the safety regulations
                                    and maintenance schedule described in this document and in the manuals  1SDH000999R0002 and
                                    1SDH001000R0002).
                                    If faults are discovered, find out what is causing them and eliminate them before putting the unit back
                                    into service.
                                           WARNING! Detecting faults must only be managed by (electrically) skilled persons (IEV
                                           195-04-01: person with relevant education and experience to enable him or her to perceive
                                           risks and to avoid hazards which electricity can create), as it may be necessary to perform
                                           insulation and dielectric tests on part or all the installation


               Alarms displayed and  A list of faults that may appear on the Ekip Touch display is given below along with suggestions on how
                       suggestions to resolve them:
                                     Signal         Suggestions
                                     Numerical alarm
                                     (e.g. 30002)  Internal error; contact ABB if this typoe of error occurs
                                                   Unit on with auxiliary supply, Local Bus parameter enabled but connection
                                                   to modules not present, incorrect or communication lost (for more than five
                                     Local bus     seconds); check:
                                                    • connection and powering of modules in terminal box or external
                                                    • that the moldules connected are compatible with Ekip Touch
                                     Trip fail     CB has failed to open and/or current still present after a TRIP command: comply
                                     command (BF)  with the procedure proposed in the next chapter 'Faults, causes and remedies'
                                                   Protection parameter configuration error: make sure that threshold I4 and time
                                                   t4 are compatible with the minimum values required for self-supply
                                                   Check:
                                                    • Rating plug of model compatible with Ekip Touch and CB size
                                     Configuration   • If present, protection parameters do not conflict with size of current of unit
                                                   details on page 27)
                                                    • In the absence of Vaux threshold I4 and/or I41 > 100 A
                                                    • In the absence of Vaux time t4 and/or t41 > 100 ms
                                                    • RC protection active and Rating Plug not RC
                                                   Ekip CI module not detected or absent, with Ekip M Touch and Open Mode
                                     Ekip CI
                                                   configuration = Normal
                                                   Problem of Ekip Com Hub module with: certificates, connected devices, missing
                                     Ekip Com Hub  Com modules (RTU or with Ethernet connection), API TLS device, Hub events,
                                                   parsar configuration
                                                   Fault in Ekip Link module: check for loss of connection with one or more actors
                                     Ekip Link Bus
                                                   (modules) connected to Link Bus
                                     Ekip Sign 3T
                                     connection    Alarm for connection of one or more analog inputs to Ekip Signalling 3T module