Continued from the previous page                                ABB | SACE Emax 2
                                     Signal         Suggestions
                                     Ekip Sign 3T   One or more thresholds of the Ekip Signalling 3T module has/have been
                                     threshold     exceeded
                                     Internal error  Internal error; contact ABB if this typoe of error occurs
                                                   Fault with Ekip Com modules: synchronization problem of SNTP
                                     SNTP error
                                                   synchronization reference module
                                     Measuring Error  Measurement module parameter reading error, contact ABB
                                     Ethernet      No external cable on one or more Ekip Com modules with Ethernet connection
                                     disconnected
                                     IEEE 1588 synch  Synchronization problem of IEEE 1588 synchronization reference module
                                                   Ekip Com module detected with incorrect / not allowed MAC address, contact
                                     MAC Address
                                                   ABB.
                                     Ekip Installation  Installation error between HMI and Mainboard, contact ABB
                                     Measuring     Install Measurement module (Settings-Circuit breaker-Installation-Measuring-
                                     installation  Install) menu
                                                   Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
                                     RatingPlugInstallation
                                                   connection if there are further faults
                                                   Maintenance alarm: carry out maintenance and then reset the alarm via Ekip
                                     Maintenance
                                                   Connect (see 1SDH001330R1002)
                                     PC Power exceed The average power limit setting of the Power Controller has been exceeded
                                     Rating plug   Rating plug not present, value or size incompatible with Ekip Touch parameters
                                     Zone Selectivity   Error in zone selectivity connections (Hardware Selectivity)
                                     Diag
                                     S.G.R. Toroid  Check connection and state of toroid
                                     Sensor L1/L2/
                                     L3/Ne         Check current sensors, status of terminal and cables connecting to Ekip Touch
                                     Configuration   TFTP server enabled and/or configuration session open on module Ekip Com
                                     Session       IEC61850 or Ekip Hub
                                                   The software versions between Mainboard and display (Ekip Touch) are not
                                                   compatible with each other: To restore compatibility, please consult ABB.
                                     Software Not      NOTE: modification of all parameters is inhibited via display; if present,
                                     Compatible        protections L, I and Iinst are active and function with the parameters prior
                                                       to the alarm (parameters of previous unit are active if display has been
                                                       replaced)
                                     CB status     CB state incorrect (esample: current present but CB in open state)
                                     Switchboard
                                     Actor         Check configuration and connection of Ekip Link module
                                     communication
                                     Error
                                     TC disconnected  Check Trip coil, status of the terminal and cables connecting to Ekip Touch
                                     Contact Wear  Make sure that the contacts/poles are in good condition.