Page 54 - ACB-E1.2-E2.2-E4.2-E6.2
P. 54
Continued from the previous page ABB | SACE Emax 2
Signal Suggestions
Ekip Sign 3T One or more thresholds of the Ekip Signalling 3T module has/have been
threshold exceeded
Internal error Internal error; contact ABB if this typoe of error occurs
Fault with Ekip Com modules: synchronization problem of SNTP
SNTP error
synchronization reference module
Measuring Error Measurement module parameter reading error, contact ABB
Ethernet No external cable on one or more Ekip Com modules with Ethernet connection
disconnected
IEEE 1588 synch Synchronization problem of IEEE 1588 synchronization reference module
Ekip Com module detected with incorrect / not allowed MAC address, contact
MAC Address
ABB.
Ekip Installation Installation error between HMI and Mainboard, contact ABB
Measuring Install Measurement module (Settings-Circuit breaker-Installation-Measuring-
installation Install) menu
Install Rating Plug (Settings-Circuit breaker-Rating Plug-Install menu) and check
RatingPlugInstallation
connection if there are further faults
Maintenance alarm: carry out maintenance and then reset the alarm via Ekip
Maintenance
Connect (see 1SDH001330R1002)
PC Power exceed The average power limit setting of the Power Controller has been exceeded
Rating plug Rating plug not present, value or size incompatible with Ekip Touch parameters
Zone Selectivity Error in zone selectivity connections (Hardware Selectivity)
Diag
S.G.R. Toroid Check connection and state of toroid
Sensor L1/L2/
L3/Ne Check current sensors, status of terminal and cables connecting to Ekip Touch
Configuration TFTP server enabled and/or configuration session open on module Ekip Com
Session IEC61850 or Ekip Hub
The software versions between Mainboard and display (Ekip Touch) are not
compatible with each other: To restore compatibility, please consult ABB.
Software Not NOTE: modification of all parameters is inhibited via display; if present,
Compatible protections L, I and Iinst are active and function with the parameters prior
to the alarm (parameters of previous unit are active if display has been
replaced)
CB status CB state incorrect (esample: current present but CB in open state)
Switchboard
Actor Check configuration and connection of Ekip Link module
communication
Error
TC disconnected Check Trip coil, status of the terminal and cables connecting to Ekip Touch
Contact Wear Make sure that the contacts/poles are in good condition.
Continued on the next page
52 | © 2022 ABB | 1SDH001316R1002 - ECN000232533 Management operations | 1 - Ekip Touch maintenance and troubleshooting