Page 35 - Application Guide Semiconductor Fuse Link
P. 35

Fuse selection examples




           3-phase a.c. controller



        Select a suitable fuse from the Ferraz Shawmut square-bodied PSC range, size 30, to protect the a.c.
        controller shown in Fig.28. The equipment designer has indicated that the possibility of a 3-phase
        fault need not be considered.


        System data is as follows :

                                                    a                                        Load
        Max AC line voltage  660 V
                                                             F2
        Frequency            50 Hz                 660 V                                  100 A r.m.s
        Ambient temperature 55 °C                   a.c.
        Cooling air speed    2 m/s
                                                    b                                        Load
        Load current         100 A
        Short-circuit current  5 kA

        Continuous load      < 12 stops per day

                                                    c                                        Load
        Occasional overload  200% for 10s


                 2
                                       2
        Thyristor I t withstand 20,000 A s
                                                                        Fig.28 3-phase a.c.
        (at 8.33 ms)
        Data for the PSC size 30 is as follows :



                      a      = 130                      For continuous load with < 12 stops
                                                        per day
                             = 30
                      0o
                      B1     = 1.25                     A’2 = 0.8 (see Table 2)
                             = 0.85
                      C1
                      Cf3     = 0.75



        First estimate the required continuous current rating

                                                               130-55
                                                           -
                                                                       =      0.866
        correction for ambient temperature     A1    =                     130 - 30

        correction for non-standard terminal contacts                   C1     =       0 .85


        correction for forced air cooling         B
 = 1 + (1.25 - 1)*2/5   =        1.1


        correction for load variations                                          A’2      =        0.8



        Since the r.m.s. fuse current is the same as the load current of 100A, we require that the adjusted
        fuse current rating is greater than 100A, which gives
                In’       =       In      x     A1     x    B    x   C1    x   A’2            100.0



                             In     x    0.866   x   0.85 x   1.1   x    0.8           100.0

                                                                                                                   35