Fuse selection examples
3-phase a.c. controller
Select a suitable fuse from the Ferraz Shawmut square-bodied PSC range, size 30, to protect the a.c.
controller shown in Fig.28. The equipment designer has indicated that the possibility of a 3-phase
fault need not be considered.
System data is as follows :
a Load
Max AC line voltage 660 V
F2
Frequency 50 Hz 660 V 100 A r.m.s
Ambient temperature 55 °C a.c.
Cooling air speed 2 m/s
b Load
Load current 100 A
Short-circuit current 5 kA
Continuous load < 12 stops per day
c Load
Occasional overload 200% for 10s
2
2
Thyristor I t withstand 20,000 A s
Fig.28 3-phase a.c.
(at 8.33 ms)
Data for the PSC size 30 is as follows :
a = 130 For continuous load with < 12 stops
per day
= 30
0o
B1 = 1.25 A’2 = 0.8 (see Table 2)
= 0.85
C1
Cf3 = 0.75
First estimate the required continuous current rating
130-55
-
= 0.866
correction for ambient temperature A1 = 130 - 30
correction for non-standard terminal contacts C1 = 0 .85
correction for forced air cooling B
= 1 + (1.25 - 1)*2/5 = 1.1
correction for load variations A’2 = 0.8
Since the r.m.s. fuse current is the same as the load current of 100A, we require that the adjusted
fuse current rating is greater than 100A, which gives
In’ = In x A1 x B x C1 x A’2 100.0
In x 0.866 x 0.85 x 1.1 x 0.8 100.0