Page 36 - Application Guide Semiconductor Fuse Link
P. 36

Fuse selection examples



                 This gives  In     154.4 A.



                 This fuse can be used in a.c. systems up to a maximum of 760V, which is above the requirement of
                 the application.



                 Choose the next higher rating in the product series, which is 160A. To confi rm that this fuse will
                                                     2
                 protect the thyristor, the let-through I t will need to be evaluated at a voltage of 0.65 x 660 = 429V
                 (assuming the selection is based on a line-line fault condition). Published data for this fuse is as
                 follows :


                               2
                                                            2
                 Total clearing I t at 700V          9400 A s
                 Peak let-through current at 5kA     2.428 kA
                 2
                 I t correction factor at 429V       0.560


                                      2
                                                                                         2
                 So the total clearing I t in the application will be 0.560 x 9400 = 5 264 A s.
                 Assuming a triangular short-circuit current waveshape, the fault duration can be found from

                                                                  2
                                                               Ipeak  TFAULT
                                                         2
                                                         I t =--
                                                                  3

                 i.e.                                                      5264 = 2428 x 2428 x TFAULT / 3

                 which gives
                                                                                   TFAULT = 2.68 ms



                 Assuming a constant I3t for the thyristor, the thyristor withstand at 2.68 ms is (see p19)

                                                    t   0,333                2.68    0,333
                                     2
                                                                                                     2
                             I t   = I0  t0  x    ( - )           =    20,000  ( -- )      = 12895 A s
                             2
                                                    t                        10.0
                                                     0
                                                                 2
                 This is much greater than the fuse total clearing I t, so the fuse will protect the thyristor.
                 Finally check the occasional overload requirement. Referring to the 160A fuse’s time-current
                 characteristic, we fi nd that IMELT = 392.8A at the 10s point. The maximum allowable overload current
                 is Cf3 x 392.8 = 0.75 x 392.8 = 294.6A for 10s. This is acceptable as it is greater than the actual
                 overload current, which is 200% of 100A = 200A for 10s.



                 Hence, the PSC size 30 160A fuse would be suitable for this application.


                 (Note that if the equipment designer had specifi ed that a 3-phase fault must be considered, the fuse
                 2
                 I t would need to be evaluated at 0.866 x 660 = 572V).

                Regenerative 3-phase bridge



                 Find a fuse from the Ferraz Shawmut round-bodied A50QS or A70QS types which will protect the
                 bridge shown in Fig.29, when fi tted in location F1.