Fuse selection examples



        System data :
                                                                                460 V
                                                                                 a.c
        Max AC line voltage          460 V, 60Hz
        Ambient temperature          45 °C
                                                                                                    500 V
        Current loading              250 A d.c.                                                      d.c
        AC s.c. current              10 kA
                                                                                                  F1
        DC working voltage           500 V (regenerative load)
        DC load time constant        30ms

        Occasional overload          500% for 0.1s                               Fig.29 3-phase bridge
        Repetitive cyclic load       141.4% for 1 hour, then 1 hour off.
        Natural cooling
        Semiconductor devices        I t withstand  68kA s at 8.33 ms;  Peak inverse voltage 1.5kV
                                                       2
                                     2
        The fuses must have an a.c. voltage rating of at least 460V and a d.c. voltage rating with L/R = 30
        ms of at least 500V. Referring to the product datasheets these values are :


                                                     VAC         VDC at L/R=30ms

                                  A50QS              500                464
                                  A70QS               700               635


        The d.c. voltage rating of the A50QS is too low, so this type cannot be used. The A70QS however
        may be suitable. The thermal coeffi cients for this fuse type are


                      a      = 150            For a 1hour ON/OFF cycle the fuse will cool down
                                              completely between cycles so the lowest value of A’2
                             = 25
                       o
                                              must be used (see section 5)
                      B1     = 1.25
                             = 0.85
                      C1
                      Cf3         = 0.75         A’2 = 0.6



        First estimate the required continuous current rating
                                                                150 - 45

                                                             -


        correction for ambient temperature      A1    =       150 - 25   =      0.917
        correction for non-standard terminal contacts                     C1        =        0 .85



        correction for load variations                                            A’2          =        0.6


        For the 3-phase bridge the r.m.s. current in the leg at F1 is 0.577 times the average d.c. current, i.e.
        0.577 x 250 = 144.25A.

                      In’       =       In      x     A1     x   C1     x   A’2            144.25


                                     In      x   0.917    x   0.85  x   0.6           144.25

        This gives  In     308.4A.  Choose the next higher size in the series, which is 350A. To check now
                                                             2
        that this fuse will protect the thyristor, the let-through I t will be evaluated at a voltage of 0.65 x 460
        = 299V. Referring to the product datasheet for the A70QS350 we obtain :
                                                                                                                   37