Page 585 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 585

ABB  MOTOR PROTECTION AND CONTROL                                                4/37

          —
          VBC7A 3-pole mini reversing contactors – with flat pin connection

          4 to 5.5 kW
          DC operated – with safety blocking function


                                    VBC7A..F 3-pole compact design reversing contactors are space optimized control products
                                    mainly used for switching resistive or motor loads up to 690 V AC.
                                       2CDC211002F0011  •  built-in mechanical interlock and safety blocking function. The safety blocking function is trig-
                                    These reversing contactors are designed with:
                                     gered if the voltage is applied to the coil of the contactor to be switched on before the contac-
                                     tor to be switched off has dropped out. The contactor coils are designed for continuous opera-
                                     tion when the contactor is de-energised i.e. the coil is not damaged if the mechanical interlock   04
          VBC7A-30-10-F              prevents switch-on of the contactor with the coil voltage applied
                                    •  flat pin connection for plug-in wiring and shake proven connection
                                    •  control circuit: DC operated, low consumption coil (3.5 W at pull-in and at holding)
                                    •  hum-free coil
                                    •  contacts configuration 30-01 fulfills the requirements for Mirror contacts acc. to annex F
                                     of IEC/EN 60947-4-1
                                    •  no auxiliary contact block permitted for mounting
                                    •  suitable for rail or wall mounting
                                    IEC         UL/CSA     Rated control  Auxiliary Type   Order code   Pkg  Weight
                                    Rated operational  3-phase  General   circuit voltage contacts      qty  (1 pce)
                                    power  current   motor   use    Uc  fitted
                                          θ ≤ 40 °C   rating    rating
                                    400 V       480 V
                                    AC-3  AC-1
                                    kW    A     hp         V DC                                            kg
                                    VBC7A mini reversing contactors with safety blocking function
                                    5.5   20    5    600 V /   24     1 0  VBC7A-30-10-F-01  GJL1313913R0101  5  0.345
                                                     16 A             0 1  VBC7A-30-01-F-01  GJL1313913R0011  5  0.345
                                    Other types on request






























                                                                                    46.7   1.84"
                                                      96.2  3.79"                   43.7   1.72"



                                     57.5   2.26"  45.2   1.78"  42.2   1.66"





                                                                                  4.5   0.18"
                                    VBC7A
                                    Main dimensions mm, inches