          Type                                        CM-MSS.x1          CM-MSS.x2           CM-MSS.x3
          Standards
          Product standard                            EN 60947-5-1, EN 60947-8
          Low Voltage Directive                       2014/35/EC
          EMC directive                               2014/30/EC
          ATEX directive                              2014/34/EC (only ATEX variants "Selection table CM-MSx range" on page 5)
          RoHS directive                              2011/65/EC
          Electromagnetic compatibility
          Interference immunity to                    IEC/EN 61000-6-1, IEC/EN 61000-6-2
            electrostatic discharge        IEC/EN 61000-4-2 Level 3, 6 kV contact discharge, 8 kV air discharge
            radiated, radio-frequency,     IEC/EN 61000-4-3 Level 3, 10 V/m (1 GHz), 3 V/m (2 GHz), 1 V/m (2.7 GHz)
            electromagnetic field
            electrical fast transient / burst  IEC/EN 61000-4-4 Level 3, 2 kV / 5 kHz
            surge                          IEC/EN 61000-4-5 Level 3, Installation class 3, supply circuit and measuring circuit 1 kV L-L, 2 kV L-N
            conducted disturbances, induced   IEC/EN 61000-4-6 Level 3, 0.15-80 MHz, 10 V, 80 % AM (1kHz)
            by radio-frequency fields
            voltage dips, short interruptions   IEC/EN 61000-4-11 Class 3
            and voltage variations
            harmonics and interharmonics  IEC/EN 61000-4-13 Class 3
          Additional interference immunity according to product standard EN 60255-1
          (reference on EN 60255-26_2011)
   07
            radiated, radio-frequency,     IEC/EN 61000-4-3 10 V/m (80 MHz - 3 GHz)
            electromagnetic field
            conducted disturbances, induced   IEC/EN 61000-4-6 10 V at stated frequencies
            by radio-frequency fields
            damped oscillatory waves      IEC/EN 61000-4-18 Signal lines, symmetric coupling: 1 kV peak voltage
                                                      Power supply, asymmetric coupling: 2.5 kV peak voltage
          Interference emissions                      IEC/EN 61000-6-3, IEC/EN 61000-6-4
            high-frequency radiated     IEC/CISPR 22, EN 55022 Class B
            high-frequency conducted    IEC/CISPR 22, EN 55022 Class B
            high-frequency radiated       Germanischer Lloyd increased requirements in the emergency call frequency band