Page 801 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 801

ABB  MOTOR PROTECTION AND CONTROL                                                 7/11

          —

          Thermistor motor protection relays
          Technical data - CM-MSE



          Data at T a = 25 °C and rated values, unless otherwise indicated
          Supply circuit - Input circuit                      CM-MSE
          Rated control supply voltage U s power consumption  1SVR550805R9300 24 V AC approx. 1.5 A
                                                   1SVR550800R9300 110-130 V AC approx. 1.5 A
                                                   1SVR550801R9300 220-240 V AC approx. 1.5 A
          Rated control supply voltage U s tolerance          -15...+10 %
          Rated frequency                                     50-60 Hz
          Measuring circuit
          Monitoring function                             T1-T2 temperature monitoring by means of PTC sensors
          Number of sensor circuits                           1
          Sensor circuit
          Sensor type                                         PTC type A (IEC/EN 60947-8)
          Max. total resistance of sensors connected in series, cold state  ≤1.0 kW
          Overtemperature monitoring              switch-off resistance 2.0-3.0 kW
                                                   (relay de-energizes)
                                                  switch-on resistance  1.2-1.65 kW
                                                    (relay energizes)
          Maximum voltage in sensor circuit                4 kW 5 V
                                                           ∞ kW 15 V
          Maximum current in sensor circuit                   2 mA
          Maximum sensor cable length                         2 x 100 m at 0.75 mm², 2 x 400 m at 2.5 mm²
          Reaction time                                       <100 ms
          Output circuit
          Kind of output                                  13-14 1 n/o contact
          Operational principle                               closed-circuit principle (output relay de-energizes if the measured value exceeds/drops
                                                              below the adjusted threshold)                           07
          Maximum switching voltage                           250 V
          Rated operating voltage U e and       AC-12 (resistive) at 230 V 4 A
                                               AC-15 (inductive) at 230 V 3 A
          rated operating current I e
                                                DC-12 (resistive) at 24 V 4 A
                                                DC-13 (inductive) at 24 V 2 A
          AC Rating (UL 508)       utilization category (Control Circuit Rating Code) B 300
                                          maximum rated operational voltage 300 V AC
                                    maximum continuous thermal current at B 300 5 A
                                 maximum making/breaking apparent power at B 300 3600/360 VA
                                                 general purpose rating 250 V AC - 4 A
          Mechanical lifetime                                 30 x 10  switching cycles
                                                                  6
          Electrical lifetime                     at AC12, 230 V AC, 4 A 0.1 x 10  switching cycles
                                                                  6
          Maximum fuse rating to achieve short-circuit   n/c contact 10 A fast-acting
          protection                                   n/o contact 10 A fast-acting
          General data
          Dimensions                                          22.5 x 78 x 78.5 mm (0.89 x 3.07 x 3.09 in)
          Duty cycle                                          100 %
          Mounting                                            DIN rail (IEC/EN 60715)
          Mounting position                                   any
          Degree of protection                     housing / terminals IP50 / IP20
          Electrical connection
          Connecting capacity               fine strand with wire end ferrule 2 x 1.5 mm² (2 x 16 AWG)
                                          fine strand without wire end ferrule 2 x 0.75-1.5 mm² (2 x 18-16 AWG)
                                                           rigid 2 x 1-1.5 mm² (2 x 18-16 AWG)
          Stripping length                                    2 x 0.75-1.5 mm² (2 x 18-16 AWG)
          Tightening torque                                   0.6-0.8 Nm (5.31-7.08 lb.in)
          Environmental data
          Ambient temperature                           Operation -20...+60 °C
          ranges                                         Storage -40...+85 °C
          Damp heat                                IEC/EN 60068-2-30 +40 °C, 93 % RH, 4 days
          Vibration withstand                     IEC/EN 60062-2-6 10-57 Hz: 0.075 mm; 57-150 Hz: 1 g
          Isolation data
          Rated insulation voltage U i                        250 V
                                                              4 kV / 1.2 - 50 μs
          Rated impulse withstand voltage U imp
          Pollution degree                                    3
          Overvoltage category                                III
   796   797   798   799   800   801   802   803   804   805   806