Page 799 - ABB_Motor _Protection_and_Control_catalogue_20221216
P. 799

ABB  MOTOR PROTECTION AND CONTROL                                                 7/9

          —

          Thermistor motor protection relays
          Technical data - CM-MSS




          Type                                        CM-MSS.x1          CM-MSS.x2           CM-MSS.x3
          General data
          MTBF                                        on request
          Duty time                                   100 %
          Dimensions (W x H x D)          product dimensions 22.5 x 85.6 x 103.7 mm (0.89 x 3.37 x 4.08 in)
                                         packaging dimensions 97 x 109 x 30 mm (3.82 x 4.29 x 1.18 in)
          Weight                                      see "Ordering details" on page 6
          Mounting                                    DIN rail (IEC/EN 60715), snap-on mounting without any tool
          Mounting position                           any
          Minimum distance to other units        vertical 10 mm (0.394 in) if switching current > 2 A
                                               horizontal 10 mm (0.394 in) if switching current > 2 A
          Material of housing                         UL 94 V-0
          Degree of protection                  housing IP50
                                                terminals IP20
          Electrical connection                       Screw connection technology  Easy Connect Technology (push-in)
          Connection capacity   fine-strand with(out) wire end ferrule 1 x 0.5-2.5 mm² (1 x 18-14 AWG)    2 x 0.5-1.5 mm² (2 x 18-16 AWG)
                                                      2 x 0.5-1.5 mm² (2 x 18-16 AWG)
                                                  rigid 1 x 0.5-4 mm² (1 x 20-12 AWG)    2 x 0.5-1.5 mm² (2 x 20-16 AWG)
                                                      2 x 0.5-2.5 mm² (2 x 20-14 AWG)
          Stripping length                            8 mm (0.32 in)
          Tightening torque                           0.6-0.8 Nm (7.08 lb.in)      -                                  07
          Environmental data
          Ambient temperature ranges           operation -25...+60 °C (-13...+140 °F)
                                                 storage -40...+85 °C (-40...+185 °F)
          Damp heat, cyclic (IEC/EN 60068-2-30)       6 x 24 h cycle, 55 °C, 95 % RH
          Climatic class (IEC/EN 60721-3-3)           3K5 (no condensation, no ice formation)
          Vibration, sinusoidal                       5...13.2 Hz: ±1 mm; 13.2...100 Hz: 0.7 g
          Shock                                       Class 2
          Isolation data
          Rated insulation voltage U i   Supply circuit / Measuring circuit (1) 300 V AC (CM-MSS.x2: n/a)
          (IEC/EN 60947-1,          Supply circuit / Output circuits 300 V AC
          IEC/EN 60664-1)
                                Measuring circuit (1) / Output circuits 300 V AC
                                  Output circuit 1 / Output circuit 2 300 V AC
          Rated impulse withstand   Supply circuit / Measuring circuit (1) 4 kV (CM-MSS.x2: n/a)
          voltage U imp             Supply circuit / Output circuits 4 kV
          (IEC/EN 60947-1,
           IEC/EN 60664-1)      Measuring circuit (1) / Output circuits 4 kV
                                  Output circuit 1 / Output circuit 2 4 kV
          Basic insulation       Supply circuit / Measuring circuit (1) 600 V AC (CM-MSS.x2: n/a)
          (IEC/EN 60664-1)          Supply circuit / Output circuits 600 V AC
                                Measuring circuit (1) / Output circuits 600 V AC
                                  Output circuit 1 / Output circuit 2 300 V AC
          Protective separation    Supply circuit / Measuring circuit (1) yes, up to 300 V
          (IEC/EN 61140)            Supply circuit / Output circuits yes (CM-MSS.x2: n/a)
                                Measuring circuit (1) / Output circuits yes
                                  Output circuit 1 / Output circuit 2 no
          Pollution degree (IEC/EN 60664-1)           3
          Overvoltage category (IEC/EN 60664-1)       III
   794   795   796   797   798   799   800   801   802   803   804