14/18 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
ABB i-bus® KNX
Multifunction Room Automation
Overview of switching performance
SA/M SA/M SD/M LR/M UD/M ES/M ES/M
2.6.1 2.16.1 2.6.2 1.6.2 1.300.1 2.230.1 2.24.1
Outputs
2 semicon- 2 semicon-
ductor out- ductor out-
Semicon- puts puts
ductor for resistive for resistive
output, loads, loads,
2 relay
2 relay 2 relay 1 relay dimmed via inrush cur- inrush cur-
Load circuits outputs,
outputs outputs output phase inter- rent: rent:
floating
val max. 1 A, max. 1 A,
or phase continuous continuous
control current: current:
max. 700 max. 700
mA mA
250/440 250/440 250/440 250/440 115/230 115/230
U n rated voltage 24 V AC/DC
V AC V AC V AC V AC V AC V AC
I n rated current 6 AX 16 A 6 AX 6 AX 700 mA 700 mA
2 x 1…10 1 x 1…10
Control outputs – – V DC V DC – – –
(passive) (passive)
Max. output
power
300 VA at
230 V AC
Max. control current – – 30 mA 30 mA 150 VA at – –
127 V AC
Min. output
power:
2 VA
Max. cable length – – 100 m 100 m – – –
Switching current per output
AC3 operation (cos φ = 0.45) 6 A / 230 V 8 A / 230 V 6 A / 230 V 6 / 230 V – – –
EN 60 947-4-1
AC1 operation (cos φ = 0.45) 6 A / 230 V 16 A / 230 V 6 A / 230 V 6 A / 230 V – – –
EN 60 947-4-1
6 A / 250 V 16 A / 250 V 6 A / 250 V 6 A / 250 V
Fluorescent lighting load AX to EN 60 669 – – –
(70 μF) (70 μF) (70 μF) (70 μF)
100 mA / 100 mA / 100 mA / 100 mA /
14
12 V 12 V 12 V 12 V
Minimum switching capacity – – –
100 mA / 100 mA / 100 mA / 100 mA /
24 V 24 V 24 V 24 V
DC current switching capacity (resistive load) 6 A / 24 V= 16 A / 24 V= 6 A / 24 V= 6 A / 24 V= – – –
—
– = Not applicable