Page 33 - Din prodcuts 2020
P. 33

1/23       1




          —
          MCBs
          S 200 technical features




    S 200  S 200 M  S 200 M UC  S 200 P   S 200 MR     S 200 S       SU 200 M             SU 200 MR   S 200 UDC
 Data acc.   Rated voltage  V  480Y / 277 V AC;  480Y / 277 V AC;  480Y / 277 V AC  480Y / 277 V AC  480Y / 277 V AC  240 V AC  480 Y / 277   1P: ≤ 35 A: 277
 to UL /                                                                         V AC     V AC;
 CSA                                                                                      > 35 A: 240
                                                                                          V AC
                                                                                          2...4P: ≤ 35 A:
                                                                                          480 / 277 V AC;
                                                                                          > 35 A: 240
                                                                                          V AC
 1P: 60 V DC;   1P: 60 V DC;   1P: 250 V DC  480 / 277 V AC                                           1P: up to
 2P…4P: 110 V DC  2P…4P: 125 V DC  2...4P: 500 V DC                                                   125 V DC
                                                                                                      2P: up to
                                                                                                      250 V DC
 Rated interrupting capacity acc. to UL 1077  kA  6 kA AC; 10 kA DC  ≤ 25 A:   10 kA  10 kA  --
                          > 25 A:   6 kA
 Short-circuit current rating acc. to UL 489     --                  10 kA                10 kA       14 kA (UL)
 Application     Suppl. prot. for general use. Application Codes: TC2,   TC1, 0L0,  TC2, 0L0,  Ring tongue   Ring tongue
 OL0, SC: U1  SC: U1      SC: U1          terminal,                                       terminal, not
                                          not for general                                 for general use
                                          use
 Reference temperature for tripping characte-  °C  B, C, D, K, Z:   25°C  25 °C  C, K, Z: 25 °C  25 °C
 ristics
 Electrical endurance  ops.  6,000 ops (AC), 6,000 ops. (DC); 1 cycle (1s - ON, 9s - OFF)  6,000 ops. (1 cycle 1s - ON,
                                                                                          9s - OFF)
 Mechani-  Housing     Insulation group II,  Insulation group I,  Insulation group II,    Insulation group I,
 cal Data  RAL 7035  RAL 7035                          RAL 7035                           RAL 7035
    Toggle     Insulation group II, black, sealable
 Contact position indication     Marking on toggle (I ON / 0 OFF), Real CPI
 (red ON / green OFF)
 Protection degree acc.  to EN 60529     IP20*, IP40 in enclosure with cover  IP20**, IP40 in enclosure with cover
 Mechanical endurance  ops.  20,000 ops.
 Shock resistance acc.  to IEC/EN 60068-2-27     25 g - 2 shocks - 13 ms  30 g - 3 shocks - 11 ms  25 g - 2 shocks -   25 g - 2 shocks -   30 g - 3 shocks - 11 ms  25 g - 2 shocks
                                          13 ms        13 ms                              - 13 ms
 Vibration resistance acc.  to IEC/EN 60068-2-6     5g - 20 cycles at 5…150…5 Hz with load 0.8In
 Environmental conditions (damp heat)   °C/  28 cycles with 55°C/90-96% and 25°C/95-100%
 acc.  to IEC/EN 60068-2-30  RH
 Ambient temperature  °C  -25 … +55°C
 Storage temperature  °C  -40 … +70°C
   28   29   30   31   32   33   34   35   36   37   38