S 200 technical features
S 200 S 200 M S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
Data acc. Rated voltage V 480Y / 277 V AC; 480Y / 277 V AC; 480Y / 277 V AC 480Y / 277 V AC 480Y / 277 V AC 240 V AC 480 Y / 277 1P: ≤ 35 A: 277
to UL / V AC V AC;
CSA > 35 A: 240
V AC
2...4P: ≤ 35 A:
480 / 277 V AC;
> 35 A: 240
V AC
1P: 60 V DC; 1P: 60 V DC; 1P: 250 V DC 480 / 277 V AC 1P: up to
2P…4P: 110 V DC 2P…4P: 125 V DC 2...4P: 500 V DC 125 V DC
2P: up to
250 V DC
Rated interrupting capacity acc. to UL 1077 kA 6 kA AC; 10 kA DC ≤ 25 A: 10 kA 10 kA --
> 25 A: 6 kA
Short-circuit current rating acc. to UL 489 -- 10 kA 10 kA 14 kA (UL)
Application Suppl. prot. for general use. Application Codes: TC2, TC1, 0L0, TC2, 0L0, Ring tongue Ring tongue
OL0, SC: U1 SC: U1 SC: U1 terminal, terminal, not
not for general for general use
use
Reference temperature for tripping characte- °C B, C, D, K, Z: 25°C 25 °C C, K, Z: 25 °C 25 °C
ristics
Electrical endurance ops. 6,000 ops (AC), 6,000 ops. (DC); 1 cycle (1s - ON, 9s - OFF) 6,000 ops. (1 cycle 1s - ON,
9s - OFF)
Mechani- Housing Insulation group II, Insulation group I, Insulation group II, Insulation group I,
cal Data RAL 7035 RAL 7035 RAL 7035 RAL 7035
Toggle Insulation group II, black, sealable
Contact position indication Marking on toggle (I ON / 0 OFF), Real CPI
(red ON / green OFF)
Protection degree acc. to EN 60529 IP20*, IP40 in enclosure with cover IP20**, IP40 in enclosure with cover
Mechanical endurance ops. 20,000 ops.
Shock resistance acc. to IEC/EN 60068-2-27 25 g - 2 shocks - 13 ms 30 g - 3 shocks - 11 ms 25 g - 2 shocks - 25 g - 2 shocks - 30 g - 3 shocks - 11 ms 25 g - 2 shocks
13 ms 13 ms - 13 ms
Vibration resistance acc. to IEC/EN 60068-2-6 5g - 20 cycles at 5…150…5 Hz with load 0.8In
Environmental conditions (damp heat) °C/ 28 cycles with 55°C/90-96% and 25°C/95-100%
acc. to IEC/EN 60068-2-30 RH
Ambient temperature °C -25 … +55°C