Page 34 - Din prodcuts 2020
P. 34
1/24 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
1
—
MCBs
S 200 technical features
S 200 S 200 M S 200 M UC S 200 P S 200 MR S 200 S SU 200 M SU 200 MR S 200 UDC
Installa- Terminal Failsafe bi-directional cylinder-lift terminal Ring Tongue Failsafe bi-directional cylinder-lift terminal Ring Tongue --
tion Terminal Terminal
Cross-section of conductors *1 Solid / mm 2 35 mm / 35 mm 2 25 mm / 25 Line side/bottom: 35mm 2 --
2
2
(top / bottom) Stranded mm 2 Load side/top *3: 1 ... 4 mm² / 1 … 2.5 mm²
Flexible mm 2 25 mm / 25 mm 2 16 mm / 16 25 mm / 25 Line side/bottom: 35mm 2 --
2
2
2
mm 2 mm 2 Load side/top *3: 1 ... 4 mm² / 1 … 2.5 mm²
S 200 AWG 18 - 4 AWG 14 - 4 AWG 18 - 4 AWG 18 - 4 AWG --
Cross-section of busbars mm 2 10 mm / 10 mm 2 --
2
(top / bottom)
AWG 18 - 8 AWG 14 - 8 AWG 18 - 8 AWG --
Tightening Torque *2 Nm 2.8 Nm 2.8 Nm --
in-Ibs. 18 in-Ibs. 25 in-Ibs.
Screwdriver No. 2 Pozidrive
Mounting On DIN rail 35 mm acc. to EN 60715 by fast clip
Mounting position any
Supply optional Please note optional bottom optional top or bottom Please note
polarity of polarity of
device device
Dimensi- Mounting dimensions acc. to DIN 43880 Mounting dimension 1 -- Mounting
ons and dimension 1
weight
Pole dimensions (H x D x W) mm 88 x 69 x 17.5 mm 85 x 69 x 17.5 88 x 69 x 17.5 100 x 69 x 17.5 89 x 69 x 17.5 92 x 71 x 17.5 100 x 71 x 17.5 115 x 69 x 17.5 92 x 71 x 17.5
mm mm mm mm mm mm mm mm
Pole weight g approx. 115 g approx. 125 g approx. 140 g approx. 125 g approx. 100 g approx. 140g approx. 140g approx. 125 g
Combi- Auxiliary contact Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
nation Signal contact Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
with aux.
elements Shunt trip Yes Yes Yes Yes Yes Yes Yes Yes Yes Yes
Undervoltage release Yes Yes Yes Yes Yes Yes No No No No
Motor Operating Device Yes Yes Yes Yes No Yes Yes No No No
Integrated auxiliary switch Yes Yes Yes Yes No Yes No No No No
*1 Prior to connection of aluminium conductors (>= 4 mm 2 ) ensure that their contact points are cleaned,
brushed and coated with grease.
Connection of aluminium conductors is not specifically approved by third party.
All approvals according to the product standards are carried out with copper conductors.
*2 Nm-values acc. IEC / in-lbs.-values acc. UL
*3 1 ... 4 mm² (rigid or flexible wires without end sleeves); 1 … 2.5 mm² (flexible wires with end sleeves)