Page 380 - Din prodcuts 2020
P. 380

4/26             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Motor operating and autoreclosing devices for
          MCBs, RCDs and Switch Disconnectors




  4
                                    Auto-reclosing unit
                                                                     F2C-ARI                F2C-ARI30
                                    Supply                     V     12 ... 30 V a.c. +10% - 15% (50-60Hz); 12 ... 48 V d.c. +10% -
                                                                     15%
                                    Number of automatic reset attempts  3
                                    Time of reset of the auto-reset meter  sec  12          45
                                    Power consumption   12 V a.c.  VA  < 15
                                    during the operation
                                                    24 V a.c.  VA    < 22
                                                    30 V a.c.  VA    < 25
                                                    12...48 V d.c.  VA  < 20
                                    Power consumption at rest  VA    < 1.5
          F2C-ARI
                                    Waiting time between auto-reset   sec  3                30
                                    attempts
                                    Closing time at ambient temperature  sec  < 1
                                    Opening time at ambient    sec   < 0.5
                                    temperature
                                    Number of operations             < 20.000
                                    Operating temperature      °C    - 25 ... + 55
                                    Cables length of control circuit  m  < 1500
                                    Cables cross-section       mm 2  < 2.5
                                    Signaling  contact  to signal a locked   1NA + 1NC (change-over contact)
                                    state following   three auto-reset
                                    attempts (terminals 3–4–5)
                                    Current carrying capacity        5 A (250 V AC) (ohmic load)
                                    Auxiliary contact (terminals 6–7–8)  1NA + 1NC (change-over contact)
                                    Current carrying capacity        3 A (250 V AC) (ohmic load)
                                    Remote control                   By means of dry contacts
                                    Remote control terminals         Terminal 9 = closing and remote reset  contact for  locked
                                                                     state; Terminal 10 = opening contact
                                                                     Terminal 11 = common reference for control contacts, +5V
                                                                     d.c. (supplied by the motor operating device)

                                    Auto-reclosing units
                                    Function: F2C-ARI and F2C-ARI30 allow the auto-reclosing of the coupled device in case of
                                    unwanted tripping. Suitable for F 200 RCCBs up to 100 A.

                                    Description           Bbn     Order details              Price  Weight Pack
                                                          8012542                            1 piece 1 piece unit

                                                          EAN     Type code   Order code            kg    pc.
                                    Auto-reclosing unit for 2P   026655  F2C-ARI  2CSF200996R0013   0.166  1
                                    and 4P F200 RCCBs
                                    Auto-reclosing unit for 2P   064350  F2C-ARI30  2CSF200995R0013  0.166  1
                                    and 4P F200 RCCBs (30”)
   375   376   377   378   379   380   381   382   383   384   385