Page 381 - Din prodcuts 2020
P. 381
4/27
—
Motor operating and autoreclosing devices for
MCBs, RCDs and Switch Disconnectors
4
Home automatic resetting unit
F2C-ARH /F2C-ARH-T
Power supply VAC 230
Number of automatic reclosing 1
attempts
Reset time for counter of automatic sec 12
F2C-ARH reclosing attempts
Power absorbed during the operation VA (t<0.5s) 20 max
Power consumption in stand-by W 0.4 max
Number of operations ≤ 10.000
Operating temperature °C -25 ... + 55
Signal contact cable section mm² ≤ 2.5
Signal contact for the locked state 1NA (change-over contact)
(terminals 1-2)
Signal contact rated current A 3 (250V AC)
Home automatic resetting unit (for domestic and similar applications)
Function: it recloses the associated residual current device, only after having checked that
there are no effective faults in the system protected by the RCCB.
Suitable for 2-pole RCCB series with 30 mA or 100 mA sensitivities, max 63 A
Description Bbn Order details Price Weight Pack
8012542 1 piece 1 piece unit
F2C-ARH-T
EAN Type code Order code kg pc.
Home automatic resetting 732433 F2C-ARH 2CSF200992R0005 0.200 1
unit (30 mA)
Home automatic resetting 658535 F2C-ARH100 2CSF200990R0005 0.200 1
unit (100 mA)
Home automatic resetting unit with autotest (for domestic and similar applications)
Function: it recloses the associated residual current device, only after having checked that
there are no effective faults in the system protected by RCCB.
Suitable for 2-pole RCCB series with 30 mA or 100 mA sensitivities, max 63 A.
F2C-ARH-T allows the RCCB automatic test every six months.
Description Bbn Order details Price Weight Pack
8012542 1 piece 1 piece unit
EAN Type code Order code kg pc.
Home automatic resetting 733232 F2C-ARH-T 2CSF200991R0005 0.200 1
unit (30 mA) with RCCB
autotest
Home automatic resetting 593836 F2C-ARH-T100 2CSF200989R0005 0.200 1
unit (100 mA) with RCCB
autotest