Page 383 - Din prodcuts 2020
P. 383

4/29




          —
          Busbars and accessories for
          MCBs S 200, RCDs F 200 and DS 200 series



                                                                                                                       4
 Busbars PS  Busbars PS…CB  Busbars PS…BP    Busbars PS…BP-C             Busbars PS..DC
 Suitable for  MCB: S200, S200M, S200P  MCB: S200, S200M, S200P, S200MUC,   MCB: SU200M, S200UDC, S200U, S200UP  MCB: SU200M, S200UDC, S200U,   MCBs, Fuseholders E90
 RCD: F200, DDA-blocks  S200MTUC             S200UP
 Electrical   Standards  for IEC applications  for IEC / UL applications  for IEC / UL applications  for IEC / UL applications  for IEC applications
 Data  IEC/EN 60947-1  IEC/EN 60947-1  IEC/EN 60947-1  IEC/EN 60947-1    IEC/EN 60947-1
 UL1077  UL489                               UL508
 Approvals  —  UL508  UL489                  UL 489                      -
 Rated voltage Ue   1P, 2P, 3P, 4P: 690 V AC, 690 V DC  1P: 1000 V AC/DC   1P, 2P, 3P: 480 V AC  600 V AC/DC  690 V AC / 1000 V DC
 2P, 3P: 600 V AC/DC
 Rated frequency  Hz  50 / 60 Hz, DC  50 / 60 Hz  50 / 60 Hz  50 Hz (IEC) / 60 Hz (UL)  50 / 60 Hz, DC
 Current carrying capacity /   A  10 mm 2  16 mm  2  30 mm 2  18 mm 2  25 mm  2  16 mm 2
 Phase (35°C ambient   End feeding   63 A  80 A  120 A  End feeding ➀                                                              80 A  100 A  80 A (115A for cubicle size ≥ 30"x30"x10")  End    100 A  End    100 A
 temperature)  ➀                             feeding ➀                   feeding ➀

 Non-end   100 A  130 A  160 A  Non-end    160 A  200 A  Non-end feeding ➀  200 A  Non-end feeding ➀  160 A
 feeding ➀                                                              feeding ➀
 Short-circuit withstand   kA  25 kA in series with fuse NH3 355 A gG 500 V   10 kA 3 cycles @ 480 V / 100 kA Fuse Class J  10 kA in series with fuse NH3 355 A gG 500 V  10 kA 3 cycles @ 600 V / 140 kA Fuse   25 kA/0,1 s, 100 kA in series with fuse
 2
 capacity  175 A / 18 mm – 200 A / 25 mm 2   Class J 200 A               NH3 355 A gG
 Mechanical   Housing  light grey, RAL 7035
 Data  Enviromental conditions   DIN EN 60068
 acc. to
 Overvoltage category  III
 Pollution degree  2
 Installation  Cross-Section Busbar  10 mm , 16 mm , 30 mm 2  18 mm ,25 mm 2  16 mm 2  25 mm 2  30 mm 2
 2
 2
 2
 Mounting position  optional
 Supply  Feed on terminal of the device (supply side   Feed on terminal of the device (supply side   Feed on terminal of the device (supply side   Feed on terminal of the device (supply   Feed on terminal of the device (supply side optional) or
 optional) or use of feeder terminal range AST;   optional) or use of feeder terminals AST 35/... CB;   optional) or use of feeder terminals AST 35/15   side optional) or use of feeder terminal   use of feeder terminal AST 35/18 DC or AST 35/45 DC
 SZ-ESK  SZ-ESK SP  BP; SZ-ESK BP            AST 35/58 BP-C
 Accessories  Shock-protection caps  BSK, SZ-BSK  BSK CB  BSK BP  BSK BP-C
 Feeder terminals  range AST, SZ-ESK  AST 35/15.. CB; AST 35/38.. CB  AST 35/15 BP  AST 35/58 BP-C  AST 35/18 DC (for use with 1-phase busbar)
 SZ-ESK SP  SZ-ESK BP                                                    AST 35/45 DC (for use with 2-phase busbar)
 End caps  range END, PS-END, PSB-END  PS-END SP; PS-END1 SP  -  PS-END 3 BP-C  PS-END0, PS-END3
 Feeder Terminals AST , SZ-ESK  Feeder Terminals AST... CB    Feeder Terminals AST 35/15 BP    Feeder Terminals AST 35/58 BP-C
 and SZ-ESK SP  and SZ-ESK BP
 Electrical   Max. operating voltage  V  690 V AC, 690 V DC  AST.. CB 1000 V AC/DC; SZ-ESK SP 690 V AC/DC  480 V AC  1000 V AC/DC
 Data
 Current carrying capacity /   A  see below ➀  115 A ➀  115 A ➀  115 A use 75° wire
 phase                                       95 A use 60° wire
 2
                                                                2
 2
                       2
 Cross-Section  mm 2  SZ-ESK  6 - 35 mm    100 A  SZ-ESK SP  35 mm   / 2AWG flexible   SZ-ESK BP  35 mm   / 2AWG flexible    AST 35/58 BP-C    28mm  / 2AWG
 with ferrules    with ferrules
 2
 2
 6 - 50 mm    125 A  50 mm  / 1AWG solid /   50 mm  / 1AWG solid / stranded
                       2
 stranded
 mm 2  AST  6 - 25 mm      80 A  AST.. CB  35 mm   / 2AWG flexible   AST 35/15  25 mm   / 3AWG flexible
 2
                       2
 2
 with ferrules  BP  with ferrules
 6 - 50 mm    125 A  50 mm   / 1AWG solid /   35 mm   / 2AWG solid / stranded
 2
                       2
 2
 stranded
 Instruction of   When cutting the busbar, ensure that the   When cutting the busbar, ensure that the   Cutting of busbar is not permitted.  Shock protection only with mounted   The copper bus has to be cut to a length that is app.
 installation  insulation profile exceeds the copper bar by   installation profile exceeds the copper bar by   end caps ensured. For DC applications   10 mm less than the corresponding length of the plastic
 approx. 10 mm on each side. Shock protection  approx. 10 mm on each side.  the required increased clearence and   busbar housing. Toch-safe only when used with the
 only with mounted end caps ensured.  Shock protection only with mounted end caps   creepage distances needs to be   required end caps. Independant from the rated voltage
 For DC applications the required increased   ensured.  ensured.         of the devices like busbars or feeder terminals the
 clearence and creepage distances needs to be                            creepage distances and distances over the air needs to
 ensured.                                                                be considered. This is depending on the particular
                                                                         application as well as on the complete assembling.
 ➀  In case of feed in from the middle of the busbar it needs to be ensured, that the sum of junction currents per side must not exceed the max busbar current Is/phase.
 Irrespective of the current carrying capacity (Is) of the busbar, the max. rated current of the devices terminal may not be exceeded.
                            Feed in from the end of the busbar  Feed in from the middle of the busbar
   378   379   380   381   382   383   384   385   386   387   388