Page 581 - Din prodcuts 2020
P. 581

5/137




          —
          Protection and safety
          Mains power protection
          OVR 240-16A


          OVR 240-16A - Technical specification
          Electrical specification                 OVR 240-16A
          ABB order code                           7TCA085460R0361                                                     5
          Nominal voltage - Phase-Neutral Uo (RMS)  240 V
          Maximum voltage - Phase-Neutral Uc (RMS)  280 V
          Working voltage (RMS)                    200-280 V
          Frequency range                          47-63 Hz
          Current rating (supply)                  16 A or less
          Max. back-up fuse (see installation instructions)   ≤ 16 A
          Leakage current (to earth)               < 0.5 mA
          Transient specification                  OVR 240-16A
          Type 2 (BS EN/EN), Class II (IEC)
          Nominal discharge current 8/20 μs (per mode) In   5 kA
          Let-through voltage Up at In  (1)        750 V
          Maximum discharge current Imax (per mode)  (2)  10 kA
          Type 3 (BS EN/EN), Class III (IEC)
          Let-through voltage at Uoc of 6 kV 1.2/50 μs and  600 V
          Isc of 3 kA 8/20 μs (per mode)  (1, 3)
          Electrical specification                 OVR 240-16A
          Temperature range                        -40 to +80 °C
          Connection type                          Screw terminal - maximum torque 0.5 Nm
          Conductor size (stranded)                4 mm 2
          Earth connection                         Via M6 stud or earth terminal -maximum torque 0.5 Nm
          Degree of protection (IEC 60529)         IP20
          Case material                            Steel
          Weight              – Unit               0.23 kg
                              – Packaged           0.25 kg
          Dimensions                               See diagrams below





                                                                109 mm centrally                             54 mm
                                                      38 mm     M4 clearance    26 mm  39 mm

                                                                  105 mm
                                                                 M3 clearance                   120 mm

                                                                                 120 mm
                                                                                               Depth:
                                                                                               56 mm
                                                                                108 x 50 mm
                                                                 80 mm
                                                                                M4 clearance
                                                                                            25 mm max.
                                                                       25 mm





          (1)   The maximum transient voltage let-through of
           the protector throughout the test (±10%), phase
           to neutral, phase to earth and neutral to earth
          (2)   The electrical system, external to the unit,
           may constrain the actual current rating
           achieved in a particular installation
          (3)   Combination wave test within IEC/BS EN 61643,
           IEEE C62.41-2002 Location Cats C1 & B3, SS
           555:2010, AS/NZS 1768-2007, UL 1449 mains wire-in