Page 576 - Din prodcuts 2020
P. 576
5/132 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Protection and safety
Specific systems protection
OVR RF Series
5
Combined Category D, C, B tested protector (to BS EN 61643) suitable for
RF systems using coaxial cables at frequencies between DC and 2.7 GHz and
where DC power is present. Suitable for RF systems with power up to 1.9 kW.
For use at boundaries up to LPZ 0 to protect against flashover (typically the
service entrance location) through to LPZ 3 to protect sensitive electronic
equipment.
Features & benefits
• Very low let-through voltage (enhanced protection to • Very low attenuation and near unity VSWR over a wide
IEC/BS EN 62305) between all lines - Full Mode protection range of frequencies ensure the protectors do not impair
• Full Mode design capable of handling partial lightning system performance
currents as well as allowing continual operation of • Available with N, 7/16 DIN and BNC connectors
protected equipment • Easily mounted and earthed via fixtures on the base of the
• Repeated protection in lightning intense environments unit that accept M3 and M5 screws or via mounting
• Wide bandwidth means a single product is suitable for brackets
a range of applications • Additional mounting plates give increased flexibility
• Robust aluminium housing
Application Installation
Use on coaxial cables to protect RF transmitter and receiver In a building, connect in series with the coaxial cable near
systems, including electronics located at the antenna where it enters or leaves the structure, or close to the
or dish. Typical examples include cell sites, military equipment being protected. This should be as close as
communications, satellite earth stations, pager systems possible to the system’s earth star point (to enable a good
and emergency services communications systems. connection to earth). On a mast, connect in series with the
coaxial cable near the antenna/dish being protected. Install
in a radio communications room, an existing cabinet or
a suitable enclosure.
OVR RF 111421 with N female
connectors installed in series
Accessories
OVR RF BK1 Straight mounting plates OVR RF BK4 Bulkhead through DIRTY CLEAN
OVR RF BK2 90° angled mounting plate (for 4 products)
mounting plates OVR RF GDT-4 Replacement
OVR RF BK3 Bulkhead through gas discharge tube
mounting plate (single)
To
equipment
From Earth
line
NOTE: These protectors are based on a continuous transmission line with a GDT connected between this line and screen/earth, and are suited for applications where DC
is required to pass to the equipment. OVR CCTV/B and OVR CCTV/T are suitable for use on coaxial (or twisted pair) CCTV lines.
For coaxial CATV lines, use the OVR CATV/F.