8/46 ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS 2CHC 420 001 C0201
—
Energy efficiency
Control units
Control Unit CMS-700
Supply voltage [VAC] 80 – 277 (L1-N, +5%)
Frequency [Hz] 50 / 60
Power input (L1-N) [W] 5 ... 40 (dep. on number of sensors)
CMS-700 Power input, [VA] Current circuit <2 (per phase)
current transformer, secondary side
Voltage measurement range [VAC] 80 – 277 (L1, L2, L3-N)
Measurement range, [A] nominal: 5
current transformer, secondary side max.: 6
Harmonic component [Hz] up to 2000
Data rate of Modbus RTU [Baud] RS485 2-wire, 2400 ... 115 200
Refresh time ≤1 sec with max. 96 sensors
CMS-700 LAN [Mbit/s] 100
8
2
User Manual Conductor cross-section [mm ] 0.5 ... 2.5
Mounting method 35 mm DIN rail (DIN 50022)
Degree of protection IP20
Dimensions [mm] 161.5 x 87.0 x 64.9 (9 WM)
Operating temperature [°C] − 25 ... +60
Bearing temperature [°C] − 40 ... +85
Standards IEC61010-1
UL 508/ CSA C22.2 No. 14
Main circuit accuracy
Voltage ± 1 %
Current ± 1 %
Harmonic component 1 %
Active power ± 2 %
Apparent power ± 2 %
Reactive power ± 2 %
Power factor ± 0.2 %
Control Unit CMS-600 – Modbus RTU
Supply voltage [VDC] 24 (± 10 %)
Power input [W] 4 – 24 (dep. on number of sensors)
Interface RS485 2-wire
CMS-600 Protocol Modbus RTU
Data rate [Baud] 2400 ... 115200
Refresh time ≤1 sec with max. 64 sensors
Insulation strength [VAC] 400
Screw-type terminals 0.5 ... 2.5 mm , max. 0.6 Nm
2
35 mm DIN rail (DIN 50022)
Mounting method
or SMISSLINE TP plug base
Dimensions [mm] 71.8 x 87.0 x 64.9 (4 WM)
CMS-600
User Manual Operating temperature [°C] − 25 ... +70
Bearing temperature [°C] − 40 ... +85
IEC 61010-1
Standards
UL 508/ CSA C22.2 No. 14