Page 788 - Din prodcuts 2020
P. 788

8/48             ELECTRICAL INSTALL ATION SOLUTIONS FOR BUILDINGS   2CHC 420 001 C0201




          —
          Energy efficiency
          Sensors and Accessories





                           Open core sensors 18 mm

                           Sensor type                               CMS-120xx     CMS-121xx     CMS-122xx
                           Measurement range                   [A]   80            40            20
          CMS-120LA        Measurement method                        TRMS, AC 50 / 60 Hz, DC
                           Peak value of the distorted wave-form     ≤ 1.5         ≤ 3           ≤ 6
                           AC accuracy (TA = 25 °C)*                 ≤ ± 1 %
                           AC* temperature coefficient               ≤ ± 0.04 %
                           AC accuracy (TA = 25 °C)*                 ≤ ± 1.2 %     ≤ ± 1.4 %     ≤ ± 1.8 %
                           DC* temperature coefficient               ≤ ± 0.14 %    ≤ ± 0.24 %    ≤ ± 0.44 %
                           Resolution                          [A]   0.01
          CMS-120FH
                           Internal sampling rate              [Hz]  5000
  8
                           Respond time (±1 %)                 [sec]  Type 0.34
                           Max. diameter of the cable          [mm]  9.6
                           Insulation                                690 V AC  /1500 V DC
                           Operating temperature               [°C]  − 25 ... +70 / − 40 ... + 85
          CMS-120PS
                           Size        CMS-120PS series        [mm]  17.4 x 41.0 x 26.5
                                       CMS-120CA series        [mm]  17.4 x 41.0 x 29.0
                                       CMS-120DR series        [mm]  17.4 x 51.5 x 43.2
                                       CMS-120LA series        [mm]  17.4 x 41.0 x 38.9
                                       CMS-120FH series        [mm]  17.4 x 41.0 x 38.9
                           Reference standard                        IEC 61010-1 | UL508 / CSA C22.2 No 14
          CMS-120DR
                           * All accuracy specifications refer to full scale value and apply at 25° C.
                           In the case of open-core sensors, the position of the cable affects accuracy.



          CMS-120CA

                           Solid-core sensors 18 mm
                           Sensor type                               CMS-100xx     CMS-101xx     CMS-102xx
                           Measurement range                   [A]   80            40            20
                           Measurement method                        TRMS, AC 50 / 60 Hz, DC
          CMS-120PS        Peak value of the distorted wave-form     ≤ 1.5         ≤ 3           ≤ 6
                           AC accuracy (TA = 25 °C)*                 ≤ ± 0.5 %
                           AC* temperature coefficient               ≤ ± 0.036 %
                           AC accuracy (TA = 25 °C)*                 ≤ ± 0.7 %     ≤ ± 1.0 %     ≤ ± 1.7 %
                           DC* temperature coefficient               ≤ ± 0.047 %   ≤ ± 0.059 %   ≤ ± 0.084 %
                           Resolution                          [A]   0.01
          CMS-120PS        Internal sampling rate              [Hz]  5000
                           Respond time (±1 %)                 [sec]  Type 0.25
                           Max. diameter of the cable          [mm]  10
                           Insulation                          [V]   690 V AC /1500 V DC
                           Operating temperature               [°C]  − 25 ... +70 / − 40 ... + 85
                           Size        CMS-100PS series        [mm]  17.4 x 41.0 x 26.5
          CMS-120DR                    CMS-100S8 series        [mm]  26.5 x 45.5 x 31.8
                                       CMS-100DR series        [mm]  17.4 x 51.5 x 43.2
                                       CMS-100CA series        [mm]  17.4 x 41.0 x 29.0
                           Reference standard                        IEC 61010-1 | UL508 / CSA C22.2 No 14

                           * All accuracy specifications refer to the relevant full scale value and apply at 25° C.
          CMS-120CA