Page 16 - DIN HV fuse-link
P. 16

Standards








         HV fuses standard: IEC 60282-1                       German standards
         High-voltage fuses – Part 1: current-limiting fuses   Two important standards
         This part of IEC 60282 applies to all types of high-voltage   • VDE 0670 T4 is the translation of IEC 60282-1 into German
         current-limiting fuses designed for use outdoors or indoors
         on alternating current systems of 50 Hz and 60 Hz    • VDE 0670 T402: Selection of current-limiting fuses for
         and of rated voltages exceeding 1000V.                transformer circuits (German addition to VDE 0670 T4)
                                                              VDE 0670 T402 defi nes fuses with ratings 6.3A to 160A.
         This standard defi nes test set-up, fuse characteristics   All ratings over this range are automatically only VDE 0670 T4.
         and normal service conditions (without derating) like:
                                                              This standard defi nes some additional melting and non-melting
         • Operating temperature: -25°C to 40°C
                                                              gates to increase the performance of the selectivity
         • Altitude: 1000m maximum                            with LV fuses.
         It is advisable to replace all three fuse-links when the fuse-link
         on one or two phases of a three-phase circuit has operated,           International range  German range
         unless it is defi nitely known that no over-current has passed   Complies with   IEC 60282-1  IEC 60282-1
         through the unmelted fuse-links.                                      (VDE 0670 part 4)  (VDE 0670 part 4)
                                                                               IEC 60787        IEC 60787 and
                                                                                                VDE 0670 part 402
         HV fuses standard: IEC 60787                          Backup          45DB____P
         Application Guide for the selection of high-voltage   Backup                           45DB____PD*
         current limiting fuse-links for transformer circuits.  Backup, CPD    45DB____PT
                                                               Backup, CPD                      45DB____PTD*
         IEC/TR 60787, which is a technical report, serves     Backup, TH      45DB____PT-x
         as an application guide to the use, in distribution transformer
         circuit applications, of fuses complying with the requirements   Backup, TH and LPL**  45DB____PTS**
         of IEC 60282-1. Therefore, this document is informative,   * Lower power disspation
         not normative.                                       ** Very low power dissipation
         The object of this application guide is to specify criteria
         for coordination of high-voltage fuses with other circuit
         components in transformer applications and to give guidance
         for the selection of fuse-links with particular reference
         to their time-current characteristics and ratings.
         All Mersen HV DIN fuses defi ned in this presentation
         are in accordance with the IEC 60787 standard.






































      16