          Voltage   Length   Current   Ref. Number  Cat. Number  VDE   VDE   Thermal   CPD  D   I    I   3  R   P (W)   Weight
                                                                                    1
          (kV)   (mm)   rating                          T4  T402  striker     (mm)  (kA)  (A)  (mΩ)  @ In  (kg)
                  537     2    G1000115   45DB360V2P     X                    56    31,5  15   755   9    2,7
          20 / 36
                  537     4    H1000116   45DB360V4P     X                    56    31,5  20   755   32   2,7
                  537     6,3  S1000286   45DB360V6,3PTD  X  X            X   56    31.5  23   889   39   2,7
                  537     10   F1032958   45DB360V10PTS  X   X     X          56    31,5  34   529   66   2,7
                  537     16   G1032959   45DB360V16PTS  X   X     X          56    31,5  66   190   67   2,7
                  537     20   H1032960   45DB360V20PTS  X   X     X          56    31,5  95   153   84   2,7
                  537     25   J1032961   45DB360V25PTS  X   X     X          56    31,5  110  118   100  2,7
          20 / 36
                  537    31,5  K1032962   45DB360V32PTS  X   X     X          65    20   135   82    119  3,7
                  537     40   L1032963   45DB360V40PTS  X   X     X          65    20   200   63    176  3,7
                  537     50   M1032964   45DB360V50PTS  X   X     X          88    20   220   40    183  6,5
                  537     63   C1018327   45DB360V63PTS  X   X     X          88    36   260   31,9  165  6,5
                  537     80   F1018330   45DB360V80PTS  X   X     X          88    36   350   24,2  230  6,5