Page 13 - DIN HV fuse-link
P. 13
®
Limitor -G General Purpose fuse-links
according to IEC 60282-1
Selection table
Rated voltage range Transformer output [kVA]
of fuse-link [kV] Mode of protection
Service voltage of Rated current of fuse-link [A] rel. short-circuit voltage U = 4% U = 5%
K
K
transformer [kV] 50 100 125 160 200 250 315 400 500 630 800 1000
Transformer rated current [A] 2,9 5,8 7,2 9,2 11,5 14,4 18,2 23,1 28,9 36,4 46,2 57,7
6/12
Rated current of fuse-link [A] 6,3 6,3-10 10 16 16 16-25 25 25-40 40 40-50 50 50
10
Transformer rated current [A] 1,5 2,9 3,6 4,6 5,8 7,2 9,1 11,5 14,4 18,2 23,1 28,9
10/24
Rated current of fuse-link [A] - 4 4-6,3 6,3 6,3-10 10 16 16 16 25 25 25
20
Table 5
Catalog Reference Range Un In L D I 1 R P (W) I²t Weight
Number Number (kV) (A) (mm) (mm) (kA) (mΩ) @ In (kA²s) (kg)
45DG120V6,3P W1000151 General Purpose, striker 6/12 6,3 292 65 40 128 6 2 2,3
45DG120V10P X1000152 General Purpose, striker 6/12 10 292 65 40 70 8 3,8 2,3
45DG120V16P Y1000153 General Purpose, striker 6/12 16 292 65 40 35 10 14 2,3
45DG120V25P Z1000154 General Purpose, striker 6/12 25 292 65 40 20,5 15 36 2,3
45DG120V40P A1000155 General Purpose, striker 6/12 40 292 78 40 12,2 24 110 3,1
45DG120V50P B1000156 General Purpose, striker 6/12 50 292 88 40 9,9 31 150 3,7
45DG240V4P C1000157 General Purpose, striker 10/24 4 442 78 40 280 5 1,8 4,1
45DG240V6,3P D1000158 General Purpose, striker 10/24 6,3 442 78 40 256 11 2 4,1
45DG240V10P E1000159 General Purpose, striker 10/24 10 442 78 40 135 15 3,6 4,1
45DG240V16P F1000160 General Purpose, striker 10/24 16 442 78 40 70,3 21 14 4,1
45DG240V25P G1000161 General Purpose, striker 10/24 25 442 88 40 41,2 31 39 4,5
Time-current characterictics
Fig. 13 Fig.14
6/12 kV 10/24 kV
13