PROTECTION TRIP UNITS                                                             3/17



















                                                                                                                       03
                           Supply                                      SACE Emax 2 trip units are always supplied with
                           SACE Emax 2 protection trip units are self-sup-  an internal battery that enables the cause of a
                           plied through the current sensors installed on the   fault to be indicated after a trip, without limit of
                           circuit breaker and do not require any external   time. This battery also ensures the update of time
                           supply devices for basic protection and alarm in-  and date, thus guaranteeing the chronology of
                           dication functions. A three-phase current of 100A   any events. When the unit switched off, the bat-
                           is sufficient for the activation. All protection set-  tery test can be run by simply pressing the iTest
                           tings are stored in non-volatile memory that   key on the front.
                           maintains the information without power supply.
                           The Ekip Supply module can be easily connected   Grey platform
                           to both direct and alternating current to activate   The previous Ekip trip units and their accessories
                           additional functions such as:               are now available as spare parts only.
                           •  Using the unit when the circuit breaker is
                            opened
                           •  Using additional modules such as Ekip Signal-
                            ling and Ekip Com
                           •  Connection to external devices such as Ekip
                            Multimeter
                           •  Recording the number of operations
                           •  G protection with values below 100A or 0.2 In
                           •  Zone selectivity
                           •  Gext and MCR protection functions