3/22             SACE EMA X 2 LOW VOLTAGE AIR CIRCUIT-BRE AKERS



          —

          Technical characteristics for protection


          trip units


          Protection functions




          ABB Code ANSI Code Function              Threshold            Threshold   Trip time              Time                  Excludibility  Excludibility  Pre-allarm  Trip curve Ekip Touch  Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
                                                                        step                               Step                              trip
          VU     47      Voltage unbalance protection  U14 = 2…90% Un unbalance  1%Un  with unbalance > U14, t14 =  0.5...60s  0.5s  yes     yes      no            t = k
                         Tolerance                 ± 5%                          The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          UF     81L     Underfrequency protection  f12 = 0.9….0.999 x fn  0.001 x fn  with f < f12, t12 =  0.06…300s  0.01s     yes         yes      no            t = k
                         Tolerance                 ± 1% (with fn ±2%)            The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          OF     81H     Overfrequency protection  f13 = 1.001….1.1 x fn  0.001 x fn  with f > f13, t13 =  0.06…300s  0.01s      yes         yes      no            t = k
                         Tolerance                 ± 1% (with fn ±2%)            The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          RP     32R     Reverse active power protection  P11 = -1…-0.05 Sn  0.001 Sn  with P > P11, t11 =  0.5…100s  0.1s       yes         yes      no            t = k
                         Tolerance                 ± 10%                         The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          ABB:   47      Cyclical direction of the phases  1-2-3 or 3-2-1                                                        yes         only     no            -
          Cyclical                                                                                                                           signalling
          direction
          ABB:   78      3phase Power factor       PF3 = 0.5…0,95       0.01                                                     yes         only     no            -
          Power                                                                                                                              signalling
          factor
          LC1/2          Current threshold         LC1 =50%...100% I1   1%                                                       yes         only     no            -
          Iw1/2                                    LC2 =50%...100% I1   1%                                                                   signalling
                                                   Iw1 = 0.1…10 In      0.01 x In
                                                   Iw2 = 0.1…10 In
                                                   Activation: up/down
                         Tolerance                 ± 10%
          S2     50TD    Time-delayed overcurrent protection I5 = 0.6...10 x In  0.1 x In  With I > I5, t5 =  0.05...0.8s  0.01s  yes        yes      no            t = k
                 68      Zone selectivity                                        t5sel = 0.04…0.2s         0.01s                 yes         yes
                         Start up                  Activation: 0.6…10 x In  0.1 x In  Range: 0.1…30s       0.01s                 yes
                         Tolerance                 ± 7% I ≤ 6 x In               The better of the two data:
                                                   ± 10% I > 6 x In              ± 10% or ± 40 ms
          D      67      Directional overcurrent protection   I7 = 0.6...10 x In  0.1 x In  with I > I7, t7 =  0.1...0.8s  0.01s  yes        yes      no            t = k
                         (forward &/or backward)
                 68      Zone selectivity                                        t7sel = 0.1…0.8s          0.01s                 yes
                         Start up (forward &/or backward)  Activation: 0.6…10 x In  0.1 x In  Range: 0.1…30s  0.01s              yes
                         Trip direction            forward &/or backward
                         Minimum angle direction (°)  3.6, 7.2, 10.8, 14.5, 18.2, 22,
                                                   25.9, 30, 34.2, 38.7, 43.4, 48.6,
                                                   54.3, 61, 69.6
                         Tolerance                 ± 7% I ≤ 6 x In               The better of the two data:
                                                   ± 10% I > 6 x In              ± 10% or ± 40 ms
          UV2    27      Undervoltage Protection   U15 = 0.5….0.98 x Un  0.001 x Un  with U < U15, t15 =  0.05…120s  0.01s       yes         yes      no            t = k
                         Tolerance                 ± 2%                          The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          OV2    59      Overvoltage protection    U16 = 1.02….1.5 x Un  0.001 x Un  with U > U16, t16 =  0.05…120s  0.01s       yes         yes      no            t = k
                         Tolerance                 ± 2%                          The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          UF2    81L     Underfrequency protection  f17 = 0.9….0.999 x fn  0.001 x fn  with f < f17, t17 =  0.15…300s  0.01s     yes         yes      no            t = k
                         Tolerance                 ± 1% (with fn ±2%)            The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms  (for t≥5s)
          OF2    81H     Overfrequency protection  f18 = 1.001….1.1 x fn  0.001 x fn  with f > f18, t18 = 0.15...300s  0.01s     yes         yes      no            t = k
                         Tolerance                 ± 1% (with fn ±2%)            The better of the two data: ± 10% or  ±
                                                                                 40 ms (for t<5s) / ± 100 ms (for t≥5s)
          S(V)   51V     Voltage controlled overcurrent   I20 = 0.6...10 x In  0.1 x In  With I > I20, t20 =  0.05…30s  0.01s    yes         yes      no            t = k
                         protection
                         Step mode                 Ul= 0.2…1 x Un       0.01 x Un
                                                   Ks= 0.1…1            0.01
                         Linear mode               Ul= 0.2…1 x Un       0.01 x Un
                                                   Uh= 0.2…1 x Un       0.01 x Un
                                                   Ks= 0.1…1            0.01
                         Tolerance                 ± 10%                         The better of the two data: ± 10% or
                                                                                 ± 40 ms (for t<5s) / ± 100 ms (for t≥5s)