Page 45 - Sace Emax 2 Catalogue
P. 45

PROTECTION TRIP UNITS                                                            3/21



















                                                                                                                       03
 ABB Code ANSI Code Function  Threshold  Threshold   Trip time  Time   Excludibility  Excludibility  Pre-alarm  Trip curve Ekip Touch  Ekip Hi-Touch  Ekip G Touch  Ekip G Hi-Touch
 step  Step           trip
 L  49  Overload Protection  I1 = 0.4…1 x In  0.001 x In  with I = 3 I1, t1 = 3...144 s  1s  yes, with rating  no  50...90% I1 step 1% t = k / I 2
          plug L=off
 Thermal Memory  yes
 Tolerance  trip between 1.05 and 1.2 x I1  ± 10% I ≤ 6 x In / ± 20% I > 6 x In
 49  Overload Protection  I1 = 0.4…1 x In  0.001 x In  with I = 3 I1, t1 = 3...144 s   1s  yes, with rating  no  50...90% I1 step 1%  t =  t1xaxb
 Standard inverse SI: k=0.14 α=0,02   plug L=off  If  k -1
 Very Inverse VI: k=13.5 α=1                    I1
 Extremely Inverse EI: k=80 α=2
 Tolerance  trip between 1.05 and 1.2 x I1  ± 10% I ≤ 6 x In / ± 20% I > 6 x In
 S  50TD  Time-delayed overcurrent protection I2 = 0.6...10 x In  0.1 x In  With I > I2, t2 =  0.05...0.8s  0.01s  yes  yes  no  t = k
 68  Zone selectivity  t2sel = 0.04…0.2s  0.01s  yes
 Start up  Activation: 0.6…10 x In  0.1 x In  Range: 0.1…30s  0.01s  yes
 Tolerance  ± 7% I ≤ 6 x In   The better of the two data:
 ± 10% I > 6 x In  +-10% or +-40ms
 51  Time-delayed overcurrent protection I2 = 0.6...10 x In  0.1 x In  with I = 10 In, t2 =  0.05...0.8s  0.01s  yes  yes  no  t = k / I 2
 Thermal Memory  yes
 Tolerance  ± 7% I ≤ 6 x In   ± 15% I ≤ 6 x In
 ± 10% I > 6 x In  ± 20% I > 6 x In
 I  50  Istantaneous overcurrent protection I3= 1.5...15 x In  0.1 x In  With I > I3, instantaneous  -  yes  (3)  no  no  t = k
 Start up  Activation: 1.5…15 x In  0.1 x In  Range: 0.1…30s  0.01s  yes
 Tolerance  ± 10%  ≤ 30 ms
 68  Zone selectivity  ≤ 30 ms  yes
 G  50N TD  Earth fault protection  I4  = 0.1...1 x In  0.001 x In  with I > I4, t4 =  Instantaneous   0.05s  yes  yes  50...90% I4 step 1% t = k
 (1)
 (with Vaux) + 0,1...1 s
 68  Zone selectivity  t4sel = 0.04…0,2s  0.01s  yes
 Start up  Activation: 0.2…1 x In  0.02 x In  range: 0.1…30s  0.01s  yes
 Tolerance  ± 7%  The better of the two data: ± 10% or
 ± 40 ms or 50ms with
 t4 = instantaneous
 51N  Earth fault protection  I4  = 0.1...1 x In  0.001 x In  with I = 4 In, t4 =  0.1…1s  0.05s  yes  yes  50...90% I4 step 1% t = k / I 2
 (1)
 Tolerance  ± 7%  ± 15%
 IU  46  Current unbalance protection  I6 = 2…90% In unbalance  1%In  with unbalance > I6, t6 =  0.5…60s  0.5s  yes  yes  no  t = k
 Tolerance  ± 10%  The better of the two data: ± 10% or ±
 40 ms (for t<5s) / +-100ms (for t≥5s)
 2I  50  Programmable instantaneous   I31 = 1.5…15 x In   0.1xIn  with I>I31, instantaneous  yes  no  no  t = k
 overcurrent protection  (max setting 15kA)
 Tolerance  ± 10%  ≤ 7ms  (2)
 MCR  Closing on short-circuit protection  I3= 1.5...15 x In  0.1 x In  With I > I3, instantaneous   0.01s  yes  no  no  t = k
 Monitor time range: 40…500ms
 Tolerance  ± 10%  ≤ 30 ms
 Gext  50G TD  Earth fault protection  I41  = 0.1...1 x In Toroid  0.001 x In   with I > I41, t41 =  0.1…1s  0.05s  yes  yes  50...90% I41 step   t = k
 (1)
 Toroid                        1%
 68  Zone selectivity  t41sel = 0.04…0,2s  0.01s  yes
 Start up  Activation: 0.1…1 x In  0.02 x In  range: 0.1…30s  0.01s  yes
 Tolerance  ± 7%  The better of the two data:
 ± 10% or ± 40 ms
 51G  Earth fault protection  I41  = 0.1...1 x In  0.001 x In  with I = 4 In, t41 =  0.1…1s  0.05s  yes  yes  50...90% I41 step 1% t = k / I 2
 (1)
 Tolerance  ± 7%  ± 15%
 Rc  64 50N TD  Residual current protection   I∆n = 3 - 5 - 7 - 10 - 20 - 30A  with I > I∆n, t∆n =  0.06 - 0.1 - 0.2 -   Available with   no  no  t = k
 87N  Differential ground fault protection   0.3 - 0.4 - 0.5 - 0.8s  rating plug Rc
 Tolerance  - 20% ÷ 0%  140ms @ 0.06s (max trip time)
 950ms @ 0.80s (max trip time)
 UV  27  Undervoltage Protection  U8 = 0.5….0.98 x Un  0.001 x Un  with U < U8, t8 =  0.05…120s  0.01s  yes  yes  no  t = k
 Tolerance  ± 2%  The better of the two data: ± 10% or ±
 40 ms (for t<5s) / ± 100 ms (for t≥5s)
 MDGF      Modified Differential    I41= 0.1…1 x In  with I>I41, t41=0.05...1s (t=k)  0.05s  yes  yes  50...90% I41 step   t = k
 Ground Fault protection  with I>I41, t41=0.1...1s (t=k/I )  1%  t = k / I 2
 2
 Tolerance  ± 7%  The highest of 15% or 15ms
 OV  59  Overvoltage protection  U9 = 1.02….1.5 x Un  0.001 x Un  with U > U9, t9 =  0.05…120s  0.01s  yes  yes  no  t = k
 Tolerance  ± 2%  The better of the two data: ± 10% or ±
 40 ms (for t<5s) / ± 100 ms (for t≥5s)
                                                                                               Table continued on next page
   40   41   42   43   44   45   46   47   48   49   50