                    Customers Page Enabling and fields for editing the Customers page (5 information lines) that can be viewed on the display of
                                    the unit (page 130).


                         Installation Date of installation of unit


                   Load Profile Time The counter indicates the time that has elapsed since the last reset of the energy measurements. It is active
                                    and updated in the presence of at least one of the following: auxiliary supply or supply by Ekip T&P.


                          Led Alive The parameter enables the behavior of the Power led of the Trip unit and of all the connected modules to be
                                    modified; if activated (Alive Mode on), the Power leds act in the following way:
                                     •  Ekip Touch: flashes at 0.5Hz frequency
                                     •  Modules: if there are no communication errors, they synchronize with the led of Ekip Touch.
                                    If deactivated, the Power leds on the respective devices come on with a steady light.


           Open/Close Remote Direct  The parameter controls 2 different command packages for remote opening and closing:
                          Command    •  Enabled: command 7 and 8 valid (direct Open and Close commands).
                                     •  Disabled: commands 7 and 8 not valid: in this case, remote opening and closing can still be obtained
                                       using the programmable YC COMMAND and YO COMMAND functions and the Request circuit-breaker
                                       opening and Request circuit-breaker closing commands


               Change Double Set of  If activated, enables the set of parameters (Adaptive Protections) to be changed even when timing alarms
                  parameters always are in progress.
                                    Disabled by default.



         Repeat zone selectivity S/I/G  If Enabled, zone selectivity HW signals propagation logic applies in accordance with the table in the QT1
                               HW technical application notes. 1SDC007100G0205
                                    If Disabled, the HW selectivity signal is not propagated by Ekip Touch


       Zone selectivity input functions The zone selectivity inputs and certain of the outputs can be configured in this section:
                                     •  Standard: input or output operation as per standard zone selectivity logic; all selectivity functions are set
                                       as Standard. (1SDC007100G0205 or 1SDC007401G0201)
                                     •  Customized: the event that activates the zone selectivity input or output can be selected.
                                           IMPORTANT: in the Customized configuration, the only zone selectivity activation
                                               event is the one set and standard selectivity operation is therefore not active
                                           (changes should only be made by expert technical personnel).



                             Glitch The commands of Glitches 16 to 23 activate the respective glitch registers, which can be used for customizing
                                    programmable functions or output contacts.


                       Wizard Reset Reset Wizard: the Wizard window appears on Ekip Touch at the first power-on and can be used to enter
                                    some of the parameters of the unit.