2 - Additional settings
Presentation Via the service connector (via Ekip Connect) or system bus communication, you can:
A description of the different functions is given below.
Programmable States There are sixteen independent programmable states identified by the letters A, B, C, D, E, F, G, H, I, L, M, N,
O, P, Q, R, offering different solutions for event control.
Each programmable status can have two values: True or False. There are also various configuration
parameters available:
• Trigger: event or combination of several status activation events (up to 24, in AND or OR logic configuration).
• On Delay: status activation delay calculated from trigger presence onwards.
• Off Delay: status de-activation delay calculated from trigger absence onwards.
NOTE: the status activates if the trigger is present for longer than the On delay setting and
de-activates if the trigger is absent for longer than the Off delay setting
Figure 32
The statuses can be used with external module Ekip Signalling 10K, on Link Bus or with the programmable
functions, so as to convey the required signaling combination to the contacts.
Filters Measuring filters can be activated on channels S.G.R. or MDGF and Rc and V0:
• GTE filter: available if the external toroid is present (S.G.R., MDGF or Rc).
• V0 filter available with neutral connection activated
If the filter is activated, the measurements and specific protections (Gext or MDGF and Rc for GTE filter, and
V0 for V0 filter) are dealt with differently: Ekip Touch applies a pass-band filter to the signal so as to measure
the fundamental component only (50 or 60 Hz).
TAG Name, User data Tags that can be programmed by the user to facilitate remote identification of units.
NOTE: the Name TAG and communication address form the identification used by Ekip
Connect for the connected devices