Page 132 - Sace Emax 2 Manual for design engineers
P. 132

ABB | SACE Emax 2
                           Test Bus The parameter allows parameter editing via the service connector to be enabled/disabled, thereby limiting
                                    the possibility of configuring all the options on the display (in the Local mode) or via modules Ekip Com (in
                                    the Remote mode).
                                    Disabling the parameter, Local mode and using the password allow security against undesired modification
                                    by unauthorized persons to be increased.
                                           NOTE: with Test Bus= Off, communication via service connector is still guaranteed (reading
                                               enabled)
                                    Ekip Touch is supplied with the parameter set to: On.



                            System The System menu provides various options:
                                     Parameter    Description                                             Default
                                     Date         Setting the current date
                                     Time         Setting the current time
                                     Language     Setting the language in display menus                   English
                                     Password     Password setting (page 50)                              00001

                                           IMPORTANT: setting and checking Date and Time is important for all the recording
                                               functions (trips or measurements); in the event of date and time glitches, reset
                                           and if necessary replace the battery inside Ekip Touch (page 256).



                              View The View menu provides various options:

                                     Parameter    Description                                             Default
                                                  Enables the orientation of the Alarms List, Measuring Instruments and
                                     TFT orientation  Main Measurements pages to be set. The options are: Horizontal, Vertical   Horizontal
                                                  clockwise, Vertical counter-clockwise
                                                  Allows you to activate a supplementary information page, which can
                                                  be accessed by pressing the iTEST button twice from any page with a
                                     Customer page                                                        Off
                                                  diagnosis bar. The information on the new page can be configured via Ekip
                                                  Connect (page 132)
                                                  Allows the current to be displayed in the Measuring instruments page to be
                                     Ammeter Phase set from among the following options: Imax, I1, I2, I3, Ne (only in the 4P or   Imax
                                                  3P + N configuration)
                                                  Allows the voltage to be displayed in the Measuring instruments page to be
                                     Voltmeter Phase                                                      Vmax
                                                  set from among the following options: Vmax, V12, V23, V31



                       Maintenance The parameter allows an alarm, concerning maintenance of the unit, to be enabled/disabled. (page 113).
                                    Ekip Touch is supplied with the parameter set to: On.





























       130 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                          Ekip Touch - Settings | 1 - Main settings