ABB | SACE Emax 2
                       Configuration The Circuit breaker-Configuration menu, allowing the presence of the External neutral sensor to be activated,
                                    is available for the 3P CB (page 234).
                                    Activation of the configuration with External neutral (3P + N) enables:
                                     •  histograms of phase Ne in the Histograms page
                                     •  neutral current measurements
                                     •  submenu for configuring the Neutral protection (Neutral Protection)
                                     •  neutral current recording in the case of TRIP
                                    With 3P CB, the parameter is set by default as: 3P.


                  Ground protection In the earth Circuit-breaker-Protections menu of the LSIG version of Ekip Touch you can:
                                     •  activate/deactivate the presence of external toroid S.G.R and relative Gext protection (page 233, 84).
                                     •  activate the presence of Rc Toroid and relative protection (page 233, 87).
                                     •  activate/deactivate the MDGF transformer presence and relative MDGF protection.
                                           NOTE: Rc Toroid can be activated if the Measuring Measurements package and Rc version
                                               Rating plug are present; sensor presence in the menu can only be deactivated afterwards
                                           by replacing the installed Rating plug

                                    With Ekip Touch LSIG, the parameter is set by default as: Absent.


                     Line frequency Frequency adjustment is performed to set the installation frequency; the choice is between 50 Hz and 60 Hz.
                                           NOTE:the measurements are taken on the basis of the set grid frequency: incorrect configuration
                                               of the parameter may lead to abnormal measurements and protection
                                    Ekip Touch is supplied with the parameter setting that suits the ordered configuration.



                           Modules The Modules menu provides various options:
                                     Parameter     Description                                            Default
                                                   The parameter defines the mode in which the parameters are written in
                                                   the unit:
                                                    • Local: parameter editing only via the display or service connector
                                                    • Remote: parameter editing only remotely (Ekip Com modules)
                                     Local/Remote      NOTES:                                             Local
                                                         • the Remote mode requires the presence of auxiliary power
                                                       supply and Ekip Com modules, otherwise it disables automatically
                                                         • However, the Local/Remote parameter can still be edited in the
                                                       Remote mode
                                                   The parameter enables communication between the Trip unit and modules
                                                   installed via terminal box or outside the unit to be activated.
                                                   Correct communication between unit and modules is confirmed by:
                                     Local bus      • population of the Modules menu with all the modules connected  Off
                                                    • Power Leds of the modules on and synchronized like the power led of
                                                   Ekip Touch
                                                    • absence of Local Bus alarm in the diagnosis bar
                                     Ekip Signalling 4K Menu with the parameters of the Ekip Signalling 4K module, if present
                                     Ekip Measuring  Menu with the parameters of the module Measurement (page 184)
                                     -             Menu of every module connected and detected (from page 191)
                                                   Access to the LOCAL Switch On and RESET signaling functions (from
                                     Functions
                                                   page 89)