ABB | SACE Emax 2
       1 - Power Controller



                        Description The  Power Controller function allows the loads of an installation to be managed according to power
                                    consumption, for the purpose of reducing consumption and optimizing energy efficiency.
                                    All the parameters and measurements of the function are available via Ekip Connect; however, the Trip unit
                                    allows certain of them to be set and displayed, as described below.

                                           IMPORTANT: consult the Technical catalog or White paper of the function for full
                                               details (page 13, 16).



               Ekip Touch Parameter Certain configuration parameters of the function are available in the Settings - Power Controller menu 46).
                                     Parameter    Description                                             Default
                                     Enable       Activates/deactivates the function and its availability in the parameters menu OFF
                                                  Enables the configuration of each of the 15 programmable loads to be set
                                     Load Operating   (from Load 1 to Load 15); either Automatic or Manual configuration can be   Manual
                                     Mode
                                                  selected
                                                  Enables 10 power limits to be set (from Power Limit 1 to Power Limit 10);
                                     Power Limits  the value is given in kW and can be set within range: 10 kW to 10000 kW, in  10 kW
                                                  10 kW steps

                                           NOTE: to characterize the parameters of the function, it is advisable to first configure them
                                               via Ekip Connect and only then use the Trip unit to enable or modify the power limits and
                                           loads



                 Ekip Touch Measure A specific page containing the main measurements is available in the Measurements pages, with Power
                                    Controller activated:

                                     Measurement               Description
                                     Ea                        Expected energy
                                     ΔT                        Time elapsed in the evaluation window
                                     LOADS                     Number of loads monitored
                                     LOADS Shed                Number of shed loads
                                     Sp                        Load shedding priority setting
                                     T                         Evaluation window

                                    The Power Controller menu, with information concerning the 15 loads in two submenus, is available in the
                                    About page when Power Controller is activated (page 47):

                                     Submenus                  Information provided
                                     Load Input Status         Status of the loads (from Load 1 to Load 15): open or closed
                                     Load Active               Load configuration (from Load 1 to Load 15): active or inactive



























       139 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                  Ekip Touch - Additional functions | 1 - Power Controller