Page 144 - Sace Emax 2 Manual for design engineers
P. 144

ABB | SACE Emax 2
       3 - IPS Interface protections



                        Description The IPS Interface protection function allows faults to be managed in installations which are able to function
                                    thanks to the energy produced by renewable and local energy sources, especially the absence of power
                                    supply, e.g. caused by a fault on the MV voltage side.
                                    The function is available for all the Ekip Hi-Touch Trip units.
                                    All the parameters and measurements of the function are available via Ekip Connect; however, the Trip unit
                                    allows protection 59 S1, V DIR, V INV and control thresholds Voltage stability, Frequency stability and F W1
                                    to be set, as described below.
                                           IMPORTANT: consult the Technical catalog or White paper of the function for full
                                               details (page 13, 16).



         Protection 59.S1 [ANSI 59S1] The  protection  sends  a  TRIP  command if the maximum  mean  value  of  the  three  line-to-line  voltages,
                                    calculated in a 10-minute floating menu, exceeds the threshold for longer than the set time.
                                    The Protections-Advanced menu includes the protection submenu in which the parameters can be entered:
                                     Parameter    Description                                             Default
                                                  Activates/deactivates the protection and its availability in the parameters
                                     Enable                                                               Off
                                                  menu
                                                  Activates/deactivates transmission of the open command: if disabled, the
                                     Trip Enable                                                          Off
                                                  alarm and exceedance of protection time are only managed as information
                                                  Establishes the value that activates the protection.
                                     Threshold    The value is given as both absolute value (Volts) and relative value (Un) and   1,1 Un
                                                  can be set within the range: 1 Un to 1.3 Un, in 0.05 Un steps
                                                  This is the trip time of the protection; the value is given in seconds and can
                                     Time                                                                 3 s
                                                  be set within a range: 3 s to 999 s, in 3 s steps

                                    Limitations and additional functions
                                    The block functions can also be accessed by means of the service connector (via Ekip Connect) or
                                    communication via system bus (page 83).


         Protection V DIR [ANSI 27VD] If the positive sequence measured by the Trip unit exceeds or falls below threshold Upos (depending on the
                                    direction set), the corresponding alarm will be activated (no TRIP).The Protections-Advanced menu includes
                                    the protection submenu in which the parameters can be entered:
                                     Parameter    Description                                             Default
                                                  Activates/deactivates the control threshold of the parameters and their
                                     Enable                                                               Off
                                                  availability in the menu
                                                  Defines whether sequence monitoring is performed after the measured
                                     Direction                                                            Down
                                                  sequence has dropped (Down) or been exceeded (Up)
                                                  Establishes the value that activates the alarm.
                                     Threshold    The value is given as both absolute value (Volts) and relative value (Un) and   0,8 Un
                                                  can be set within the range: 0.1 Un to 1.5 Un in 0.05 Un steps




          Protection V INV [ANSI 59VI] If the negative sequence measured by the Trip unit exceeds or falls below threshold Uneg, the corresponding
                                    alarm will be activated (no TRIP).
                                    The Protections-Advanced menu includes the protection submenu in which the parameters can be entered:
                                     Parameter    Description                                             Default
                                                  Activates/deactivates monitoring of the parameters and their availability in
                                     Enable                                                               Off
                                                  the menu
                                                  Establishes the value that activates the alarm. The value is given as both
                                     Threshold    absolute value (Volts) and relative value (Un) and can be set within the range:  0,05 Un
                                                  0.05 Un to 0.5 Un in 0.05 Un steps







       142 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Additional functions | 3 - IPS Interface protections