Page 145 - Sace Emax 2 Manual for design engineers
P. 145

ABB | SACE Emax 2
                        VS Warning A warning signal is activated if all three of the line-to-line voltages measured by the Trip unit are within the
                                    window defined by the control thresholds for the set time.
                                    The Protections-Advanced-Warnings menu includes the control threshold submenu in which the parameters
                                    can be entered:
                                     Parameter    Description                                             Default
                                                  Activates/deactivates monitoring of the parameters and their availability in
                                     Enable                                                               Off
                                                  the menu
                                                  Defines whether the line-to-line voltages to be verified are those from the
                                                  internal sockets (Measurement module) or from Ekip Synchrocheck, if
                                     Signal source  present.                                              Meas.
                                                      NOTE: if Ekip Synchrocheck is set, monitoring will refer to one single
                                                     voltage
                                                  Establishes the lower limit value of the control band, given as both absolute
                                     Threshold
                                     DOWN         value (Volts) and relative value (Un), which can be set within the range: 0.5   0,9 Un
                                                  Un to 1 Un in 0.001 Un steps
                                                  Establishes the upper limit value of the control band, given as both absolute
                                     Threshold UP  value (Volts) and relative value (Un), which can be set within the range: 1 Un  1,1 Un
                                                  to 1.5 Un, in 0.001 Un steps
                                                  This is the monitoring time that activates the signal; the value is given in
                                     Time                                                                 30 s
                                                  seconds and can be set within a range: 0.1 s to 900 s, in 0.1 s steps



                        FS Warning A warning signal is activated if the frequency measured by the Trip unit is within the window defined by the
                                    control thresholds for the set time.
                                    The Protections-Advanced-Warnings menu includes the control threshold submenu in which the parameters
                                    can be entered:
                                     Parameter    Description                                             Default
                                                  Activates/deactivates monitoring of the parameters and their availability in
                                     Enable                                                               Off
                                                  the menu
                                                  Defines whether the line-to-line voltages to be verified are those from the
                                                  internal sockets (Measurement module) or from Ekip Synchrocheck, if
                                     Signal source  present.                                              Meas.
                                                      NOTE: if Ekip Synchrocheck is set, monitoring will refer to one single
                                                     voltage
                                                  Establishes the lower limit value of the control band, given as both absolute
                                     Threshold    value (Hertz) and relative value (Fn), which can be set within the range: 0.9   0,998 Fn
                                     DOWN
                                                  Fn to 1 Fn in 0.001 Fn steps
                                                  Establishes the lower limit value of the control band, given as both absolute
                                     Threshold UP  value (Hertz) and relative value (Fn), which can be set within the range: 1 Fn  1,002 Fn
                                                  to 1.1 Fn in 0.001 Fn steps
                                                  This is the monitoring time that activates the signal; the value is given in
                                     Time                                                                 30 s
                                                  seconds and can be set within the range: 0.1 s to 900 s, in 0.1 s steps



                      F W1 Warning If the frequency measured by the Trip unit exceeds or falls below the threshold (depending on the direction
                                    set), the corresponding alarm will be activated (no TRIP).
                                    The Protections-Advanced-Warnings-F W Warnings menu includes the control threshold submenu in which
                                    the parameters can be entered:

                                     Parameter    Description                                             Default
                                                  Activates/deactivates the control threshold of the parameters and their
                                     Enable                                                               Off
                                                  availability in the menu
                                                  Defines whether frequency monitoring is performed after the measured
                                     Direction                                                            Down
                                                  sequence has dropped (Down) or been exceeded (Up)
                                                  Establishes the value that activates the alarm.
                                     Threshold    The value is given as both absolute value (Hertz) and relative value (Fn) and   3 Fn
                                                  can be set within the range: 0.9 Fn to 1.1 Fn in 0.001 Fn steps






       143 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A             Ekip Touch - Additional functions | 3 - IPS Interface protections