ABB | SACE Emax 2
       4 - Introduction to the electronic accessories



                Operating conditions Ekip Synchrocheck, Ekip Com and Ekip Signalling function correctly:
                                     •  In the presence of auxiliary supply voltage
                                     •  With the circuit-breaker in the Racked-in position (if the CB version is withdrawable)
                                    The limitations listed below apply in all the other cases:

                                                                                Ekip Signalling 2K
                                     Module\         Ekip
                                     Condition       Synchrocheck  Ekip Com     Ekip Signalling 3T  Ekip Signalling 4K
                                                                                Ekip Signalling 10K
                                     Module power    Synchronism   Communication:   Output contacts: open  Output contacts:
                                     supply absent   contact open  absent                         open
                                     CB in Test  (1)(2)    Synchronism:   Communication:   Inputs and output   Inputs and output
                                     position        not available  (4)  active  contacts: available  contacts: available
                                     CB in                                      Inputs and output   Module power supply
                                     DISCONNECTED  (1)(3)    Synchronism:   Communication:   contacts: partial   off (Output contacts::
                                                                  partially active
                                                     not available
                                                                             (5)
                                                               (4)
                                     position                                   available  (6)    open)
                                    (1)  the description refers to the module when correctly on and with the CB in the indicated position
                                    (2)  in the Test position, the Trip unit is connected to the modules and all information is available on the display or
                                    via external communication
                                    (3)  in the Racked-out position, connection and communication between Trip unit and modules is interrupted.
                                    Information is not available/valid
                                    (4)  due to voltage not connected to the internal sockets
                                    (5)  see System Interface, INFORMATION WITH PROTECTION TRIP UNIT DISCONNECTED section (next page)
                                    (6)  the outputs only function correctly if configured as: input status (of module itself) or non-communication with
                                    Trip unit. For all other configurations, the module forces the Outputs as per Contact Type parameter (NO, NC).


                    System Interface Document 1SDH001140R0001.zip, describing how to use the Ekip Com communication modules correctly,
                                    is available in ABB library; the file contains:
                                     Document              Description
                                                           Guidelines with details about how to put the communication modules into
                                     1SDH001140R0001.pdf
                                                           service, with reference to the protocols and supporting documents
                                                           Table with the references of all the registers for parameters, controls,
                                     1SDH001140R0001.xlsx
                                                           measurements, etc.
                                    The .zip file contains the files for supplementing Ekip Touch in the available communication networks, with the
                                    specific Ekip Com module and an IMPORTANT file with notes on how to use the files:
                                     File  (1)(2)                  Protocol / Ekip Com module
                                     ABBS0E7F.gsd + EkiDPB.bmp     File .gsd and module image for configuring Ekip Com Profibus DP
                                     Ekip_COM_EtherNetIP_M4_v03_06.eds File .eds for configuring Ekip Com EtherNet/IP  TM
                                     Ekip_COM_DeviceNet_v02_08.eds  File .eds for configuring Ekip Com DeviceNet  TM
                                     ABBEC0304_Ed1.icd
                                     ABBEC0304_Ed2.icd             File .icd for configuring Ekip Com IEC 61850
                                     GSDML-V2.3-ABB S.p.A.-Ekip Com   File .xml for configuring Ekip Com Profinet
                                     Profinet-20180823.xml

                                    (1)  The files are also valid for the respective Redundant versions.
                                    (2)  Check the Firmware version of your module so as to choose the file with the correct configuration.


















       182 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                Accessories | 4 - Introduction to the electronic accessories