                              Menu The specific configuration area will activate in the Settings - Modules - Ekip Measuring menu if the Measurement
                                    module is detected correctly by Ekip Touch.
                                    The following parameters can be configured in this menu:

                                     Parameter        Description                                       Default
                                     Voltage Transf.  Selects the presence or absence of the external transformer  Absent
                                                      Available in the absence of a transformer; defines rated voltage Un.
                                     Rated voltage    The value is given as absolute value (Volts) and can be set within   400 V
                                                      the range: 100 V to 690 V with variable steps.
                                                      Available in the presence of a transformer; defines rated voltage Un
                                                      of the installation.
                                     Primary voltage                                                    400 V
                                                      The value is given as absolute value (Volts) and can be set within
                                                      the range: 100 V to 1150 V with variable steps.
                                                      Available in the presence of a transformer; defines the secondary
                                                      voltage of the transformer.
                                     Secondary voltage                                                  100 V
                                                      The value is given as absolute value (Volts) and can be set within
                                                      the range: 100 V to 230 V with variable steps.
                                                      Defines the power flow required for D protection; there are 2
                                                      options available (page 73):
                                     Positive Power flow   • High  → Low: the power flows from the low terminals to the high  High  → Low
                                                      ones (load connected low)
                                                       • Low  → High: opposite power flow (load connected high)
                                                      Available with 3P CB; allows the presence of the external Neutral
                                                      to be enabled.
                                     Neutral connection                                                 Absent
                                                           NOTE: presence of the neutral activates phase voltage
                                                          measurement



                             About The About-Modules menu contains the specific menu of the module with the serial number and version of
                                    the module itself.



                               Test The Measurement module must be disconnected from Ekip Touch (according to the procedure available on
                                    the front label) and the external sockets must be disconnected from the terminal box in the following cases:
                                                                                       Module Measurement enabler
                                     Test                  Module Measurement enabler  (1)
                                                                                       with voltage sockets
                                     Dielectric test                                   x
                                     Isolation between phases  x                       x

                                    (1)  disconnection to be performed also in the presence of Ekip Touch without Measuring package


                       Replacement The Measurement module can be replaced on its Trip unit, for details consult document 1SDH001000r0528.
                                    If the  Measurement module is replaced, module change is indicated on the display by an alarm in the
                                    diagnosis bar when the apparatus is powered for the first time.
                                    To install the new module:
                                     •  Confirm the installation module which appears automatically on the display
                                     •  Execute manual control, available in the Settings menu (page46)
                                           WARNING! if the Class 1 Power & Energy Metering package is present, module
                                               replacement could impair the performance values indicated on page 117; consult
                                           ABB to assess solutions able to comply with your requirements