Page 189 - Sace Emax 2 Manual for design engineers
P. 189
ABB | SACE Emax 2
Interface The module has nine signaling leds:
Figure 122
LEDs Description
Power Signals the state of the module (on or off)
Indicate the physical state of the contacts of each output:
O 01, O 02, O 03, O 04 • off: contact open
• on: contact closed
Indicate the physical state of the contacts of each input:
I 01, I 02, I 03, I 04 • off: circuit open
• on: short circuit
Menu The specific configuration area will activate in the Settings-Modules menu if the Ekip Signalling 4K module is
connected correctly to Ekip Touch.
The programming submenus of the inputs and outputs are present inside.
Output parameters All the available outputs enable the following parameters to be configured:
Parameter Description Default
Event which activates the output and changes the state of the contacts.
Different protection proposals, statuses and thresholds are available in the
Signal source None
menu; the Custom mode can be configured via Ekip Connect so as to extend
the solutions and combine several events.
Minimum presence of Source for output activation; the Delay is given in
seconds and can be set within a range between 0 s and 100 s, in 0.01 s steps.
Delay NOTES: 0 s
• output will not activate if Source deactivates before Delay has elapsed
• if delay = 0 s Source must still be present for longer than 300 mS
Defines the rest status of the contact with Source not present between either:
Contact Type normally open (NO) and closed (NC). NO
Output activation coincides with the change in state with respect to that of rest.
Allows the output to be managed differently when Source disappears: either
keep contact activated (On) or deactivate it (Off).
Latched (1) Off
NOTE: if Self-latching = On, the output resets if the module switches off,
or in the case of a module auto test or signal reset command
Continued on the next page
187 | © 2020 ABB | 1SDH001330R1002 - ECN000134959 - Rev. A Internal electronic accessories | 3 - Ekip Signalling 4K