        External electronic accessories




       1 - Ekip Supply



                                    Ekip Supply is an accessory supply module. It is available in two models, depending on the incoming voltage
                                    to be provided.
                                    It performs three functions:
                                     •  supplies auxiliary power to Ekip Touch
                                     •  allows the terminal box modules to be supplied and connected to Ekip Touch
                                     •  acts as a bridge for the Local Bus between Ekip Touch and the external electronic accessories (e.g. Ekip
                                       Signalling 10K and Ekip Multimeter)
                                    The module has a Power led to signal the presence of incoming power supply:
                                     •  off: no supply
                                     •  on (steady): supply present


             Electrical characteristics                                     Ekip Supply        Ekip Supply
                                     Model
                                                                            24-48VDC           110-240 VAC/DC
                                     Power supply voltages                  21,5 ÷ 53 VDC      105 ÷ 265 VAC/DC
                                     Frequency                              --                 45 ÷ 66Hz
                                     Maximum power consumption without modules  (1)  3 W       3 VA/W
                                     Maximum power consumption with modules  (2)  10 W         10 VA/W
                                     Maximum inrush current                 2 A for 20 ms      2 A for 20 ms

                                    (1)  Ekip Touch with just Ekip Supply
                                    (2)  Ekip Touch with three modules connected with Ekip Cartridge


                       Connections The module must be assembled in the first slot of the terminal box on the circuit-breaker (fixed version) or on
                                    the fixed part (withdrawable version).
                                    For references about the connection and terminals, please consult document  1SDM000091r0001; use
                                    AWG 22-16 cables with 1.4 mm maximum outer diameter for the external cabling.
                                    To connect the module to Ekip Touch, please consult document 1SDH001000r0511.









































       190 | © 2020 ABB |  1SDH001330R1002 - ECN000134959 - Rev. A                      External electronic accessories | 1 - Ekip Supply